Home>DCS>ABB DX571 8-Input 8-Relay-Output Digital Module

Hot Categories

ABB DX571 8-Input 8-Relay-Output Digital Module

ABB DX571 8-Input 8-Relay-Output Digital Module

Item NO.: 3756545

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameABB DX571 8-Input 8-Relay-Output Digital Module
  • Item NO.3756545
  • Weight0.1500 kg = 0.3307 lb = 5.2911 oz
  • CategoryDCS
  • BrandABB
  • Creation Time2026-09-02
ABB DX571 8-Input 8-Relay-Output Digital Module
BrandABB
ModelDX571
LifecycleActive
ABB / AC500 S500-eCo mixed relay I/O module

ABB DX571 8-Input 8-Relay-Output Digital Module

Eight 24 V AC/DC inputs and eight normally-open relay outputs divided into three galvanically isolated groups.

01

Product Identification

ABB DX571, article 1TNE968902R2302, combines eight 24 V AC/DC digital inputs with eight normally-open relay outputs. The input channels form one group, while the relay outputs form two groups of four, producing three galvanically isolated groups in total.

02

Engineering Data

Manufacturer ABB
Article Number 1TNE968902R2302
Product Family AC500 S500-eCo
Module Type Digital input/output module
Digital Inputs 8 channels, 24 V AC/DC
Digital Outputs 8 normally-open relay outputs
Output Grouping 2 groups of 4 relay channels
Galvanic-Isolation Groups 3 total: 1 input group and 2 output groups
Supported Relay Voltages 24 V AC/DC or 100-240 V AC
Maximum Relay Current 2 A at 24 V; 1.5 A at 120/240 V AC pilot duty
Process Supply 24 V DC at L+
Process-Supply Current 50 mA
Recommended Output Protection 3 A fast-acting fuse
Maximum Module Dissipation 2.3 W
Terminal Blocks One 9-pin and one 11-pin block, ordered separately
Lifecycle Active
03

Functions

  • Reads eight 24 V AC or DC field signals through one isolated input group.
  • Switches eight loads through normally-open relay contacts arranged as two output groups.
  • Provides individual yellow state indication for each input and relay output.
  • Maintains galvanic separation between the input group, both output groups and module electronics.
  • Uses removable terminal blocks to support organized S500-eCo field wiring.
04

Applications

  • Mixed AC/DC sensor monitoring with relay-actuated field circuits in one module.
  • Contactor, pilot and alarm control within the documented relay contact limits.
  • S500-eCo installations that require two independently isolated groups of four outputs.
  • Maintenance replacement where normally-open relay behavior and three-group isolation must be retained.
  • Control panels needing 24 V inputs and higher-voltage relay switching from the same station slot.
05

Lifecycle

  • ABB lists DX571 article 1TNE968902R2302 in the Active lifecycle phase.
  • Retain the 9-pin and 11-pin terminal-block selection in the equipment record.
  • DX561 uses transistor outputs and should not replace the relay-based DX571 without circuit redesign.
  • External contact protection and appropriate voltage segregation remain necessary.
  • Test the input group and both relay groups independently after replacement.