A 24 V DC compact controller with 128 kB memory, mixed onboard I/O, Ethernet and separately ordered pluggable terminal blocks.
Technical Summary
PM564-TP-ETH, article 1SAP120900R0071, is an AC500-eCo processor module with 128 kB memory and an integrated Ethernet interface. The onboard signal set combines six digital inputs, six transistor outputs, two analog inputs and one analog output for compact control panels.
The P designation identifies the pluggable-terminal construction. The CPU is supplied without the removable I/O terminal blocks, so one 9-pole and one 11-pole terminal block must be selected for a complete installation.
Specifications
| Manufacturer | ABB |
|---|---|
| Product Family | AC500-eCo |
| Model | PM564-TP-ETH |
| Article Number | 1SAP120900R0071 |
| Program Memory | 128 kB |
| Supply Voltage | 24 V DC |
| Digital Inputs | 6 channels |
| Digital Outputs | 6 transistor channels |
| Analog Inputs | 2 channels |
| Analog Outputs | 1 channel |
| Ethernet | Integrated |
| Terminal Style | Pluggable; terminal blocks ordered separately |
| Required Terminal Blocks | One 9-pole and one 11-pole block |
| Configurable Channel Context | Analog inputs can be configured as digital inputs |
| Lifecycle | Classic |
Features
- Runs compact AC500-eCo control applications from 128 kB program memory.
- Combines digital, transistor and analog channels in one processor module.
- Provides onboard Ethernet for engineering and supported controller communication.
- Allows the two analog input points to be used as digital inputs when the application is configured accordingly.
- Uses removable terminal blocks to support service access without permanent fixed terminals.
- Accepts local AC500-eCo expansion when the application needs additional I/O.
Compatibility
- Requires the AC500-eCo engineering and firmware environment used by this CPU generation.
- Needs the correct 9-pole and 11-pole pluggable terminal blocks because they are not supplied with the processor.
- Transistor output loads must remain within the documented DC output ratings and wiring arrangement.
- The Ethernet address and application communication settings must be restored from the installed project.
- Do not substitute the relay-output or AC-supply PM564 variants without reviewing field loads and controller power.
Replacement
- PM564-TP-ETH is in the Classic lifecycle phase and should be planned as an installed-base product.
- ABB identifies PM5032-T-ETH as a possible migration device, but it is not a drop-in exchange.
- A migration review must include the onboard channel count, transistor outputs, analog functions, terminal conversion, program and Ethernet services.
- Archive the application, firmware, IP configuration and I/O map before removing the existing CPU.
- Test every onboard channel and network exchange after a like-for-like replacement or modernization.
FAQ
Does PM564-TP-ETH include its terminal blocks?
No. One 9-pole and one 11-pole pluggable terminal block must be ordered or retained separately.
What does the P in the model identify?
It identifies the pluggable-terminal construction of this AC500-eCo CPU.
Which onboard outputs are fitted?
The processor provides six transistor digital outputs and one analog output.
Can the analog inputs serve another role?
The two analog input channels can be configured as digital inputs when the application requires it.
Is PM5032-T-ETH a direct replacement?
It is a migration candidate, not a direct exchange; the project, terminals, I/O and firmware must be reviewed.
Which details matter for a service spare?
Confirm article 1SAP120900R0071, 24 V DC supply, Ethernet use, terminal-block set and the complete onboard I/O assignment.
Recommended Models
| KP6B 060-519166 | M200,52121556 | MSO1350 293656958 |
| FST-951A-IV | 3RV2021-1BA20 | 23846462 |
| 6ES7326-1BK01-0AB0 | DIN-INT-00-08 | JZ10-11-R10 |
| 2866679 QUINT-PS/1AC/48DC/5 | CL-PKZ2 | 613XB/6130BKN000000 |
| C-Bus2 L5504RVF | CAD32GD TeSys-04025 | RC87618222 |
| QND-6082R | 2215-23327-001 | Nov-54 |
| EG103E | S972LX IS23DI0XCD000 | Rex2000 D42 |
| GV2ME16 | 192X2254 | BZMB1-A40-BT |
| DI561 / 1TNE968902R2101 | 21029771 | HTXRC12A2 |
| 6ED1052-1CC01-0BA8 6ED1055-1CB10-0BA2 | ipLDK-60 L60-VOIB | PGM-2602 M032-4111-200 |