ABB TA5105-4DOT Digital Output Option Board
A four-channel 24 V DC transistor-output option board for AC500-eCo V3 processors, rated at 0.5 A per channel and supplied with a removable seven-pin spring terminal.
Product Profile
TA5105-4DOT extends a compatible AC500-eCo V3 processor with four non-latching transistor outputs in one electrically isolated group. Each channel is designed for 24 V DC loads up to 0.5 A.
The seven-pin removable terminal carries outputs O0 through O3 together with the UP process supply and ZP reference. Four yellow LEDs indicate the commanded output states when the required module and process supplies are present.
Technical Data
| Manufacturer | ABB |
|---|---|
| Model | TA5105-4DOT |
| Order Code | 1SAP187000R0002 |
| Controller Family | AC500-eCo V3 |
| Output Channels | 4 transistor outputs |
| Channel Grouping | One group of four channels |
| Rated Process Voltage | 24 V DC |
| Maximum Current per Channel | 0.5 A |
| Maximum Current per Group | 2 A |
| Output Operation | Non-latching |
| Minimum High-State Voltage | UP minus 0.1 V |
| Turn-On Delay | 50 microseconds at rated load |
| Turn-Off Delay | 200 microseconds at rated load |
| Output Data Length | 1 byte |
| Leakage Current at Signal 0 | 0.5 mA maximum |
| Output Protection | Non-protected; external fuse required for each channel |
| Maximum Cable Length | 500 m shielded; 150 m unshielded |
| Field Terminal | Removable 7-pin spring/cable-front terminal, 3.50 mm pitch |
| Lifecycle Phase | Active |
System Role
The option board adds a compact group of standard digital outputs directly at the processor. The CPU supplies the board logic, while UP and ZP provide the external process supply for the output stage.
Output LEDs provide channel-state indication, but the load circuit still depends on correct process power, external protection and application wiring.
Compatibility
- Install only in an AC500-eCo V3 processor option slot that supports TA5105-4DOT.
- Use the full model and order code because TA5105-4DOTW is a separate wide-temperature variant.
- Provide external short-circuit and overload protection because the outputs are not internally protected.
- Do not connect two outputs in parallel.
- Remove CPU and process power before mounting, removing or rewiring the option board.
Applications
- Switching four 24 V DC resistive or pilot-duty loads from an AC500-eCo V3 processor.
- Compact machine control where a small local output expansion is required.
- Output-state monitoring through the four front yellow LEDs during commissioning.
- Panel retrofits that retain a compatible CPU and need the same seven-pin terminal arrangement.
- Replacement of the standard TA5105-4DOT after the wide-temperature requirement and process-load current are checked.
FAQ
What is the complete model represented by TA5105?
The complete product designation is TA5105-4DOT, order code 1SAP187000R0002.
How much current can each output switch?
Each of the four transistor outputs is rated for a maximum of 0.5 A at 24 V DC.
Are the outputs short-circuit protected?
No. ABB specifies external protection and warns against short-circuiting or overloading the channels.
What are UP and ZP used for?
UP supplies positive 24 V DC process power and ZP is the 0 V reference for the output group.
Can two outputs be wired in parallel?
No. Parallel connection of two outputs is not permitted.
May the board be inserted or removed while powered?
No. CPU supply and process voltage must be switched off before mounting, removal or wiring work.
Recommended Models
| 4906GY | RS485 4683-TTM-1F | b3850 |
| TBS50 15855 | T-100-G | STP100-50 |
| LA305-S/SP1 | TRIO-PS-2G/1AC/24DC/10 | E1411B 75000 |
| ML2-6 | ABB/BBC GJR2242000R1 LR370A-E 9060/035 | ABL7 RE2410 |
| EV45 | NBB2-8GM30-E2-0.5M-V1 119737 | DI-8 02-5B-7F-BB-51-00 |
| N3510TA-M | 5791100 | ABB TP857 / 3BSE030192R1 |
| DSP-2 v2 ,EN54-16 ,F01U101303 | TE-6300W-110 | DN33E9HR20 |
| ABB DC523 A0 1SAP 440500R0001 | HSN-6A | MFM384-RC |
| 1756-PSCA2 | IQ8MCP 804973.F0 | 03608 |