Warranty: 1 year
Condition : brand new in factory sealed box
Email: sales@mvme.cn
Chat online: +86 18030175807
10.4-inch color HMI with analog resistive touch input, EtherNet/IP and RS-232 communications, and 24V DC power.
The Allen-Bradley 2711P-T10C4D1 is a PanelView Plus 1000 operator terminal. It combines a 10.4-inch color active-matrix TFT display with analog resistive touch input, EtherNet/IP and RS-232 communication interfaces, and 24V DC input power. Rockwell Automation identifies this catalog number as discontinued.
| Catalog Number | 2711P-T10C4D1 |
|---|---|
| Product Family | PanelView Plus 1000 |
| Display | 10.4 in color active-matrix TFT LCD |
| Display Area | 211 × 158 mm |
| Resolution / Color | 640 × 480; 18-bit color |
| Operator Input | Analog resistive touch; 1 million presses; 10...110 g operating force |
| Backlight | CCFL; 50,000 h minimum at 25 °C |
| Communications | EtherNet/IP and RS-232 |
| Internal Flash | 64 MB; 20 MB application flash for Series A–D logic modules |
| Expansion | Type I CompactFlash, up to 512 MB |
| Input Power | 24V DC nominal; 18...32V DC |
| Power Consumption | 70 W maximum; 39 W typical at 24V DC |
| Dimensions (H × W × D) | 248 × 329 × 55 mm |
| Panel Cutout (H × W) | 224 × 305 mm |
| Approximate Weight | 2.6 kg |
| Operating Temperature | 0...55 °C |
| Storage Temperature | −25...70 °C |
| Relative Humidity | 5...95%, noncondensing |
| Maximum Altitude | 2000 m |
| Enclosure Ratings | NEMA 12, 13, 4X indoor; IP54; IP65 |
| Shock | 15 g operating; 30 g nonoperating at 11 ms |
PanelView Plus terminals are configured with FactoryTalk View Machine Edition Station applications. Rockwell Automation's migration guidance states that PanelView Plus applications at version 3.2 or later can be migrated to PanelView Plus 7 terminals. The application should be backed up, converted in a supported FactoryTalk View Studio environment, validated for the destination firmware, and functionally tested before production use.
Typical uses include operator control and monitoring, machine status and diagnostics, alarm and event display, production data entry, and visualization for EtherNet/IP-connected automation systems.
2711P-T10C4D1 lifecycle status: Discontinued.
Manufacturer discontinuation date: December 31, 2012.
The catalog number is no longer part of Rockwell Automation's active product offering. Availability shown on this site relates to existing inventory and does not change the manufacturer's lifecycle status.
Rockwell Automation's product lifecycle information identifies 2711P-T10C4D8 as the direct catalog conversion for 2711P-T10C4D1. Because 2711P-T10C4D8 is also discontinued, its engineering replacement is 2711P-T10C22D9P.
| Catalog Number | Manufacturer Position | Replacement Level | Key Considerations |
|---|---|---|---|
| 2711P-T10C4D8 | Direct catalog conversion; discontinued December 30, 2021 | Historical direct conversion | Not the current active choice. |
| 2711P-T10C22D9P | Engineering replacement; Active / Preferred | Current recommended migration path | Not a completely identical, no-change replacement. Mechanical, communications, display, firmware, and application review are required. |
| 2711P-T10C21D8S | PanelView Plus 7 Standard option | Alternative only where Standard limits are acceptable | Maximum 100 screens, 500 alarms and one controller; Ethernet, touch and DC configuration. The Performance adapter plate is not specified for this Standard terminal. |