Emerson A6500-CC AMS 6500 ATG System Communication Card
The rack communication card that reads AMS 6500 ATG module data and serves Modbus or OPC UA interfaces.
Overview
A6500-CC is the Emerson AMS 6500 ATG System Communication Card. It reads parameters from protection modules and outputs data through Modbus TCP/IP, Modbus RTU and/or OPC UA to control and third-party systems.
The one-slot card also supports rack configuration, local graphical displays, SNTP time synchronization and an SD card used by AMS 6500 ATG Prediction functions. Two communication cards can be used for a redundant data path.
Specs
| Manufacturer | Emerson |
|---|---|
| Exact Model | A6500-CC |
| Product Family | AMS 6500 ATG |
| Product Type | System Communication Card |
| Data Protocols | Modbus TCP/IP, Modbus RTU and OPC UA |
| Ethernet | RJ45, 10/100 Mbit/s, maximum 100 m cable |
| Serial Interface | RS-485; Modbus RTU at 9600 or 19.2 kBaud |
| USB | USB Type B, 12 Mbit/s |
| Assignable Modbus Registers | 2000 |
| Rack Form | 3U, one-slot plug-in module |
| Rack Slots | Communication slots CD13 and CD14 in supported A6500 system racks |
| Power Consumption | Maximum 6 W |
| Protection Class | IP20 |
| Operating Temperature | -20 to +70 °C with forced cooling; -20 to +55 °C without forced cooling |
| Relative Humidity | 5–95%, non-condensing |
| Configuration | Password protected; hot-swappable module |
Features
Collects machinery-protection parameters from AMS 6500 ATG cards for external systems.
Supports Ethernet, serial and OPC UA data paths with redundant communication options.
Provides rack configuration access and local-display support.
Includes self-monitoring of hardware, power input and internal temperature.
Applications
- Integration of AMS 6500 ATG machinery-protection data with DeltaV, Ovation or third-party systems.
- Redundant communication paths for critical steam, gas, compressor and hydro-turbomachinery monitoring.
- Local rack-display and prediction-data applications using the documented system architecture.
Lifecycle
- Export the communication-card configuration, register map, network settings and security record.
- Record rack type, communication slot, companion card, firmware and connected systems.
- Verify IP addresses, serial settings, OPC UA clients, SNTP and display connections before replacement.
- After installation, test each configured data path, time synchronization, rack polling and redundancy behavior.
FAQ
Can A6500-CC run Modbus TCP and Modbus RTU at the same time?
The card supports multiple configured data outputs and redundant-path use; confirm the exact rack configuration and client plan before commissioning.
What network information should accompany an enquiry for A6500-CC?
Provide rack type and slot, firmware, IP settings, serial parameters, OPC UA use, register map and any redundant-card arrangement.
Why must the communication slot be checked for A6500-CC?
The card is installed in designated communication positions, and the rack layout determines the supported arrangement and redundancy plan.
What should be tested after replacing A6500-CC?
Verify module polling, Modbus clients, OPC UA sessions, serial links, SNTP, local displays and redundant switchover where configured.
How can a mismatched register map affect A6500-CC?
Communication may remain online while external tags read the wrong parameters, so the approved map must be compared before service release.
Recommended Models
| K.2DPS5.PC/17 | OAW-AP1201H | 6AV6545-4BA16-0CX0 |
| 2CDG110091R0011 | 718579 REV B | IPC6-100 |
| KP1-ETH 6058-042.277563 / 6058-042.270338 | G0111332 G052.003730.010.006.010 | Linde BMF-140 |
| NJ20+U1+A2 | TYF642F 890-8222-00 | 37-1016-01 DB9 RS232 |
| 46904 KHA6-SH-Ex1 | Siemens 6FQ1292-1A | SC90 SC 90AF021 |
| DSQC 328 3HAB | 1606771 LEHC 002054 | TT-MJC-7.5M/25FT-MC-BLK |
| 690 25D011411/N | 70-778-01 | X20 SO 2530 |
| MGB-L1B-PNC-R-117020 | MB-G6-24-R | E9066N 866THQHKPZ |
| 3LT12.5-460/220/-23 8-010-012003 | MU210A | BW2276 149501-51033 |
| 7D0138.70 | LBPS2501AS2 | 440E-L13137 |