Home>DCS>Emerson / GE Fanuc IC693MDL753H Series 90-30 DC Output Module

Hot Categories

Emerson / GE Fanuc IC693MDL753H Series 90-30 DC Output Module

Emerson / GE Fanuc IC693MDL753H Series 90-30 DC Output Module

Item NO.: 3792231

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameEmerson / GE Fanuc IC693MDL753H Series 90-30 DC Output Module
  • Item NO.3792231
  • Weight0.2800 kg = 0.6173 lb = 9.8767 oz
  • CategoryDCS
  • BrandEmerson
  • Creation Time2026-10-13
Thirty-two sourcing outputs in four isolated groups

Emerson / GE Fanuc IC693MDL753H Series 90-30 DC Output Module

A 12/24 VDC positive-logic output module whose H hardware revision must remain part of the replacement identity.

ManufacturerEmerson / GE Fanuc
Exact modelIC693MDL753H
Product typeSeries 90-30 32-Point DC Positive Logic Output Module
01

Key Information

IC693MDL753H is a Series 90-30 discrete output module with 32 sourcing outputs arranged as four groups of eight. Each group has its own common and can serve a different compatible load supply.

The H suffix identifies the installed hardware revision. Selection should preserve the complete IC693MDL753H label, connector arrangement and Series 90-30 application record.

02

Functions

01

Switches positive-side DC power to field loads from 32 PLC-controlled output points.

02

Separates the field circuits from the backplane logic through optical isolation.

03

Provides four independently supplied output groups so compatible 12 VDC and 24 VDC loads can be organized by group.

04

Shows point status through front-panel indicators and forces all outputs off when the CPU stops.

03

Specifications

Manufacturer Emerson / legacy GE Fanuc
Product family Series 90-30
Module type DC positive-logic discrete output
Output count 32 points, four isolated groups of eight
Rated voltage 12/24 VDC
Operating output range 10.2 to 28.8 VDC
Output current 0.5 A per point; 4 A maximum per group
Common-pin current 3 A maximum per group common pin
Inrush capability 5.4 A for 10 ms
On-state voltage drop 0.3 VDC maximum
Off-state leakage 0.1 mA maximum
Response time 0.5 ms maximum on; 0.5 ms maximum off
Backplane current 260 mA maximum from the 5 VDC bus
Field connection Two front 24-pin male connectors
Hardware revision H
04

Installation

  • De-energize the field supply and verify the four group commons before removing the installed module.
  • Use both common pins where group current requires it, and keep every group within the point, group and connector-current limits.
  • Map the right connector to groups A and B and the left connector to groups C and D before transferring field wiring.
  • Confirm the slot is configured as a 32-point output module using 32 discrete output bits, then test outputs group by group.
05

Lifecycle

  • Retain the H revision, module label and connector-cable identity in the spare record.
  • Inspect the two high-density connectors for bent pins, heat discoloration and strain before installation.
  • Record measured load current and field-supply voltage after commissioning to create a useful replacement baseline.

About IndustryParts

https://www.industryparts.com/

Revision-controlled output-module replacement

IndustryParts keeps the H revision, two-connector arrangement and four-group field wiring visible throughout an IC693MDL753H enquiry.

  • Complete revision retained
  • Connector evidence reviewed
  • Group loading documented
IndustryParts office operations team
07

FAQ

Can IC693MDL753H replace another IC693MDL753 revision without review?

Do not assume revision interchangeability. Confirm the CPU and baseplate support record, connector set and any site qualification tied to the installed H revision.

What wiring evidence should be sent for an IC693MDL753H enquiry?

Provide the full module label, both connector part numbers, group-common wiring and the voltage used by each output group.

Why should both common pins be checked on IC693MDL753H?

Each common pin is limited to 3 A. High-current group wiring may require both pins so the connector path remains within its rating.

What should incoming inspection cover for IC693MDL753H?

Check the H suffix, connector pins, housing latches, terminal-cable retention and evidence of overheating or field contamination.

What is the safest commissioning sequence for IC693MDL753H?

Energize with outputs inhibited, verify each group supply and common, then command one point at a time while checking the actual load current.

Enquiry Information

Send the complete IC693MDL753H label, quantity and destination for an exact enquiry record.

WHATSAPP / PHONE+86 18030175807

You May Also Like