Home>DCS>Emerson IC200ALG265G 15-Channel 15-Bit Analog Voltage Input Module, Revision G

Hot Categories

Emerson IC200ALG265G 15-Channel 15-Bit Analog Voltage Input Module, Revision G

Emerson IC200ALG265G 15-Channel 15-Bit Analog Voltage Input Module, Revision G

Item NO.: 3809146

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameEmerson IC200ALG265G 15-Channel 15-Bit Analog Voltage Input Module, Revision G
  • Item NO.3809146
  • Weight0.1000 kg = 0.2205 lb = 3.5274 oz
  • CategoryDCS
  • BrandEmerson
  • Creation Time2026-10-26
VersaMax I/OINDUSTRY PARTS · CONTROLLED PRODUCT RECORD
VERSAMAX ANALOG INPUT · 15 SINGLE-ENDED CHANNELS · G REVISION

Emerson IC200ALG265G 15-Channel 15-Bit Analog Voltage Input Module, Revision G

A high-density VersaMax voltage-input module with the installed G suffix preserved for controlled service.

MANUFACTUREREmerson
EXACT MODELIC200ALG265G
PRODUCT TYPE15-Channel 15-Bit Analog Voltage Input Module, Revision G
Input range−10 to +10 V
Resolution15 bit
Module update7.5 ms
01
PRODUCT DOSSIER

Key Information

IC200ALG265G is the G-revision identity of the VersaMax IC200ALG265 high-density voltage input module. The base module accepts fifteen single-ended channels in one group.

Manufacturer documentation publishes a −10 to +10 V input range, 15-bit conversion and a 7.5 ms update for the complete module. It also identifies internal-hardware and loss-of-user-side-power diagnostics.

The G suffix is retained as part of the installed label. No electrical change is inferred solely from the suffix without a matching Emerson revision notice.

02
OPERATING ROLE

Functions

A

High-density acquisition

Samples fifteen single-ended voltage signals without distributing them across multiple lower-density modules.

B

Bipolar measurement range

Converts signals across the documented negative-to-positive ten-volt span.

C

Module-level diagnostics

Reports internal hardware and user-side power conditions available to the VersaMax system.

D

Backplane transfer

Places fifteen analog words into the controller data exchange on each published update cycle.

03
MANUFACTURER DATA

Specifications

Manufacturer Emerson Exact model IC200ALG265G
Base catalog IC200ALG265 Installed revision G
Signal type Analog voltage input Channels 15 single-ended, one group
Input range −10 to +10 V Resolution 15 bit
Input impedance 100 kΩ Analog data 15 words
Update rate 7.5 ms Input filter response 32 Hz ±20%
Typical accuracy at 25 °C ±0.3% of full scale Fault withstand ±30 V
DOCUMENTED INDUSTRIAL SUPPLY

About IndustryParts

https://www.industryparts.com/

Exact-model handling for IC200ALG265G

IndustryParts keeps the complete model label, requested quantity, application evidence and delivery requirements together so the proposed supply can be checked against the installed system before dispatch.

IndustryParts industrial automation supply support
04
CONTROLLED WORK

Installation

Capture the scaling

Record engineering units, alarm limits, channel usage and cable shield treatment for all active inputs.

Check external conditions

Confirm source commoning, user-side power and that no field circuit exceeds the published fault limit.

Verify measured values

Compare each restored channel with a traceable source and record raw and scaled readings.

05
SERVICE RECORD

Lifecycle

Revision trace

Keep the G suffix visible on purchase, receipt and installation records.

Calibration context

Trend channel offsets and retain the test instrument and tolerance used for periodic checks.

Diagnostic history

Archive user-power and internal-hardware events before clearing faults.

07
CUSTOMER QUESTIONS

FAQ

Q01

Does the G suffix change the published base specification of IC200ALG265G?

No suffix-specific electrical change is assumed here; the G marking is retained as the exact installed revision.

Q02

What loop information should accompany a IC200ALG265G enquiry?

Provide the channel list, source ranges, scaling, common arrangement, shield practice and the complete module label.

Q03

How much controller data does IC200ALG265G exchange?

The manufacturer documentation assigns fifteen analog input words to the module.

Q04

Which fault condition is important before changing IC200ALG265G?

Investigate loss of user-side power and internal-hardware diagnostics before treating the module as failed.

Q05

How is IC200ALG265G proved after service?

Apply known bipolar voltage points to used channels and confirm raw counts, engineering scaling and alarm behavior.