Emerson IC200ALG265G 15-Channel 15-Bit Analog Voltage Input Module, Revision G
A high-density VersaMax voltage-input module with the installed G suffix preserved for controlled service.
Key Information
IC200ALG265G is the G-revision identity of the VersaMax IC200ALG265 high-density voltage input module. The base module accepts fifteen single-ended channels in one group.
Manufacturer documentation publishes a −10 to +10 V input range, 15-bit conversion and a 7.5 ms update for the complete module. It also identifies internal-hardware and loss-of-user-side-power diagnostics.
The G suffix is retained as part of the installed label. No electrical change is inferred solely from the suffix without a matching Emerson revision notice.
Functions
High-density acquisition
Samples fifteen single-ended voltage signals without distributing them across multiple lower-density modules.
Bipolar measurement range
Converts signals across the documented negative-to-positive ten-volt span.
Module-level diagnostics
Reports internal hardware and user-side power conditions available to the VersaMax system.
Backplane transfer
Places fifteen analog words into the controller data exchange on each published update cycle.
Specifications
| Manufacturer | Emerson | Exact model | IC200ALG265G |
|---|---|---|---|
| Base catalog | IC200ALG265 | Installed revision | G |
| Signal type | Analog voltage input | Channels | 15 single-ended, one group |
| Input range | −10 to +10 V | Resolution | 15 bit |
| Input impedance | 100 kΩ | Analog data | 15 words |
| Update rate | 7.5 ms | Input filter response | 32 Hz ±20% |
| Typical accuracy at 25 °C | ±0.3% of full scale | Fault withstand | ±30 V |
About IndustryParts
https://www.industryparts.com/Exact-model handling for IC200ALG265G
IndustryParts keeps the complete model label, requested quantity, application evidence and delivery requirements together so the proposed supply can be checked against the installed system before dispatch.
Installation
Capture the scaling
Record engineering units, alarm limits, channel usage and cable shield treatment for all active inputs.
Check external conditions
Confirm source commoning, user-side power and that no field circuit exceeds the published fault limit.
Verify measured values
Compare each restored channel with a traceable source and record raw and scaled readings.
Lifecycle
Revision trace
Keep the G suffix visible on purchase, receipt and installation records.
Calibration context
Trend channel offsets and retain the test instrument and tolerance used for periodic checks.
Diagnostic history
Archive user-power and internal-hardware events before clearing faults.
Related Models
FAQ
Does the G suffix change the published base specification of IC200ALG265G?
No suffix-specific electrical change is assumed here; the G marking is retained as the exact installed revision.
What loop information should accompany a IC200ALG265G enquiry?
Provide the channel list, source ranges, scaling, common arrangement, shield practice and the complete module label.
How much controller data does IC200ALG265G exchange?
The manufacturer documentation assigns fifteen analog input words to the module.
Which fault condition is important before changing IC200ALG265G?
Investigate loss of user-side power and internal-hardware diagnostics before treating the module as failed.
How is IC200ALG265G proved after service?
Apply known bipolar voltage points to used channels and confirm raw counts, engineering scaling and alarm behavior.