Home>DCS>Emerson IC694ALG223-FC RX3i Analog Current Input Module

Hot Categories

Emerson IC694ALG223-FC RX3i Analog Current Input Module

Emerson IC694ALG223-FC RX3i Analog Current Input Module

Item NO.: 3788604

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameEmerson IC694ALG223-FC RX3i Analog Current Input Module
  • Item NO.3788604
  • Weight1.0000 kg = 2.2046 lb = 35.2740 oz
  • CategoryDCS
  • BrandEmerson
  • Creation Time2026-10-11
PACSYSTEMS RX3I | 16 CURRENT INPUTS | FC HARDWARE REVISION

Emerson IC694ALG223-FC RX3i Analog Current Input Module

An FC-revision, high-density RX3i module for sixteen single-ended 0–20 mA or 4–20 mA analog input channels.

BrandEmerson / GE Fanuc
ModelIC694ALG223-FC
Product TypeRX3i 16-Channel Analog Current Input Module
01

Key Information

IC694ALG223-FC is the FC hardware execution of the PACSystems RX3i IC694ALG223 high-density analog current input module. The module provides sixteen single-ended current inputs for 0–20 mA or 4–20 mA field loops.

The complete FC suffix should remain in the quotation, receiving record and installed asset history. Electrical function follows the IC694ALG223 family, while revision-specific interchangeability must be checked against the rack, firmware and site change-control record.

02

Functions

  • Acquires sixteen single-ended process-current signals in one RX3i module position.
  • Supports both 0–20 mA and 4–20 mA input ranges.
  • Converts field currents to controller data with documented 12-bit resolution.
  • Updates the complete module data set on the documented scan schedule.
  • Provides a high-density analog input option for rack-based RX3i control systems.
03

Specifications

Manufacturer Emerson / GE Fanuc
Model IC694ALG223-FC
Base Catalog Number IC694ALG223
Hardware Revision FC
Product Family PACSystems RX3i
Product Type High-density analog current input module
Input Channels 16 single-ended
Input Ranges 0–20 mA and 4–20 mA
Resolution 12 bit
Module Update Time 13 ms
Backplane Current 120 mA at 5 VDC
User-Supplied Power 65 mA at 24 VDC
Agency Listing UL and UL hazardous-location listing
Approvals CE Zone 2, ATEX, Class I Division 2 and listed marine approvals
Mounting Context RX3i rack-based I/O installation
Revision Control Match FC suffix, rack configuration and controller project
04

Installation

  • Export the analog configuration, scaling, alarm limits and channel references before removing IC694ALG223-FC.
  • Photograph the FC label, slot, terminal assembly, commons, shield terminations and external 24 VDC wiring.
  • Confirm loop polarity and isolate or safely drive every current loop before disconnecting the module.
  • Restore channel ranges and scaling from the approved PAC Machine Edition project.
  • Inject known currents across all used channels and verify raw values, engineering units, alarms and controller logic.
05

Lifecycle

  • Keep the FC suffix with calibration, rack and project records.
  • Trend open-loop, underrange and overrange events so wiring faults are not misclassified as module failures.
  • Inspect terminal condition, loop supply and shield practices during planned maintenance.
  • Do not assume BB, FC or another revision is interchangeable without the approved Emerson compatibility record.
07

FAQ

What information prevents an IC694ALG223-FC revision mismatch?

Send the complete IC694ALG223-FC label, rack and slot, controller model, PAC Machine Edition release, terminal photographs and the installed module revision list.

Can a 4–20 mA loop be moved to IC694ALG223-FC without checking the project?

No. Confirm the configured range, scaling, diagnostics, alarm treatment, loop supply and channel reference before transferring wiring.

How should an IC694ALG223-FC spare be acceptance-tested?

Use traceable current injection on every required channel, verify raw and scaled values, exercise alarm limits and retain the project checksum and test record.

What should be included when an IC694ALG223-FC reading is unstable?

Provide loop-supply measurements, shield and grounding details, field-device type, terminal condition, channel trend and comparison results from a known current source.

Can IC694ALG223-FC replace IC694ALG223-BB automatically?

Not from the base catalog number alone. Compare revision support, rack hardware, firmware, project validation and any manufacturer change notices before approval.

You May Also Like