Home>DCS>Emerson IC695ALG616 16-Channel Single-Ended / 8-Channel Differential Analog Input Module

Hot Categories

Emerson IC695ALG616 16-Channel Single-Ended / 8-Channel Differential Analog Input Module

Emerson IC695ALG616 16-Channel Single-Ended / 8-Channel Differential Analog Input Module

Item NO.: 3805367

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameEmerson IC695ALG616 16-Channel Single-Ended / 8-Channel Differential Analog Input Module
  • Item NO.3805367
  • Weight0.1800 kg = 0.3968 lb = 6.3493 oz
  • CategoryDCS
  • BrandEmerson
  • Creation Time2026-10-23
CURRENT OR VOLTAGE INPUT · 16 SINGLE-ENDED / 8 DIFFERENTIAL

Emerson IC695ALG616 16-Channel Single-Ended / 8-Channel Differential Analog Input Module

An RX3i analog input module configurable for sixteen single-ended or eight differential current/voltage channels.

01
PRODUCT CONTEXT

Technical Summary

Emerson IC695ALG616 is a PACSystems RX3i analog current/voltage input module. It supports sixteen non-isolated single-ended points or eight differential points, selected through the approved hardware configuration.

Supported mode choices include current and voltage ranges such as 4–20 mA and −10 to +10 V. The chosen mode determines scaling, wiring and the channel count used by the application.

System planning must account for the RX3i CPU, carrier constraints, backplane power and the module features that may not pass through every remote expansion carrier.

02
ENGINEERING RECORD

Specifications

ManufacturerEmerson
Exact modelIC695ALG616
Product familyPACSystems RX3i
Input typeAnalog current or voltage
Single-ended architecture16 non-isolated channels
Differential architecture8 channels
Example configured ranges4–20 mA; −10 to +10 V
Minimum RX3i CPU version3.00
3.3 V backplane load450 mA / 1.485 W
5 V backplane load600 mA / 3 W
Carrier limitationCEE001 carriers do not support this module’s fault reporting or interrupts
03
CAPABILITY MAP

Features

01

Selectable channel architecture

The project can use the high-density single-ended map or the differential arrangement required by the signal design.

02

Current and voltage acquisition

Configured input modes support common process-current and bipolar-voltage measurements.

03

RX3i diagnostics

Module and channel status can participate in the controller diagnostic strategy when the host path supports those features.

04

Software-defined scaling

Engineering conversion and alarm use follow the selected input mode and the controlled machine project.

INDUSTRIAL AUTOMATION SUPPLY SUPPORT

About IndustryParts

https://www.industryparts.com/

Exact-model handling for IC695ALG616

IndustryParts keeps the complete IC695ALG616 identity, requested quantity and installed-system evidence together so the proposed supply can be checked against the actual application before dispatch.

Complete label retained with the enquiry
Installed-system evidence reviewed before quotation
Exact requested quantity linked to the model record
IndustryParts industrial automation support team
04
SYSTEM BOUNDARIES

Compatibility

A

CPU and configuration

Confirm RX3i CPU firmware, programming software support and the exact hardware configuration.

B

Carrier path

Do not assume every remote carrier passes fault and interrupt behavior required by the application.

C

Field circuit

Record single-ended or differential wiring, range, transmitter supply, shield and common strategy for each point.

05
SERVICE SEQUENCE

Replacement

STEP 1

Export the channel design

Preserve mode, range, scaling, alarms, filter and diagnostic handling for all configured points.

STEP 2

Audit rack loading

Check both 3.3 V and 5 V backplane budgets and the actual local or remote carrier path.

STEP 3

Run measured tests

Apply traceable references to every used channel and verify values, limits, diagnostics and application response.

06
CUSTOMER DECISION SUPPORT

FAQ

Q01

When does IC695ALG616 use eight rather than sixteen channels?

The eight-channel map is used for differential inputs; the sixteen-channel arrangement is the non-isolated single-ended architecture.

Q02

What carrier check matters for IC695ALG616?

Confirm the exact local or remote carrier because CEE001 paths do not support this module’s fault reporting or interrupts.

Q03

Which project data prevents a mismatched IC695ALG616 setup?

Supply each channel’s wiring form, current or voltage range, scaling, filter, alarm handling and diagnostic requirements.

Q04

Why should both backplane supplies be reviewed for IC695ALG616?

The module draws from both the 3.3 V and 5 V rails, so a rack-load review must include each published demand.

Q05

What should be demonstrated after installing IC695ALG616?

Use traceable input references to prove every active point, then verify configured alarms, fault reporting and controller logic response.