Emerson IC695ALG704-CB PACSystems RX3i Four-Channel Analog Output Module
A four-channel RX3i analog output module with individually configured current or voltage operation and a complete CB hardware identity.
Technical Summary
PRODUCT CONTEXTIC695ALG704-CB provides four software-configurable analog outputs for PACSystems RX3i control applications. Each channel can be enabled independently and assigned one of the manufacturer-published current or voltage ranges. Latching alarms, engineering-unit scaling and channel defaults are configured in the controller project rather than by hardware jumpers.
The complete CB suffix should stay with the equipment record. The base module installs only in an RX3i Universal Backplane, requires an external 24 V DC field supply at the terminal block and uses a separately ordered 36-terminal removable terminal assembly.
Specifications
CONTROLLED DATA4, non-isolated
0–20 mA; 4–20 mA
−10 to +10 V; 0–10 V
PACSystems RX3i Universal Backplane
Release 3.0 or later
PAC Machine Edition 5.0 SP3 or later
375 mA at 3.3 V DC
150 mA at 24 V DC
IC694TBB032, IC694TBB132, IC694TBS032 or IC694TBS132
Features
FUNCTIONAL DISTINCTIONSChannel-by-channel configuration
Enable status, range, scaling, offset, alarm limits and clamp limits are controlled individually for each output.
Predictable fault response
The project can hold the last commanded value or drive a configured default when the CPU is stopped or communication is lost.
Diagnostic supervision
The module reports configuration, field-power and output-channel conditions to the controller for maintenance review.
Automatic calibration
Internal calibration support reduces the need for field adjustment while keeping the project settings traceable.
About IndustryParts
https://www.industryparts.com/Controlled handling for IC695ALG704-CB
IndustryParts keeps the submitted IC695ALG704-CB identity, requested quantity and installed-system evidence together so a proposed supply can be checked before dispatch.
- Complete submitted model retained
- Installed-system evidence reviewed
- Quotation record kept with the enquiry
Compatibility
SELECTION BOUNDARIESRack position
Use an RX3i Universal Backplane position supported by the installed CPU and project; do not place the module in a Series 90-30-only rack.
Field termination
Select the terminal style required by the wiring method and preserve its keying and conductor schedule during exchange.
Power connection
Apply the external 24 V DC source to the terminal assembly as documented; the backplane terminal TB1 is not the field-power connection for this module.
Replacement
SERVICE WORKFLOWRecord
Export the controller project and capture channel ranges, scaling, alarm limits, default values and the complete CB label.
Transfer
De-energize the rack and field supply, retain the keyed terminal assembly and install the exact hardware identity without moving conductors.
Commission
Restore the approved project, confirm field power and prove every active output with the receiving device under the site procedure.
FAQ
CUSTOMER DECISION SUPPORTCan IC695ALG704-CB mix current and voltage outputs?
Yes. The four channels are configured individually, so the approved project may assign current and voltage ranges to different channels.
Does IC695ALG704-CB include its removable terminal block?
No. Emerson lists the compatible box-style and spring-style terminal assemblies as separately ordered items.
What should accompany a IC695ALG704-CB enquiry?
Provide the complete CB label, terminal-block catalog number, project version, channel range schedule and requested quantity.
May IC695ALG704-CB be installed in any RX3i-labeled rack?
It requires an RX3i Universal Backplane and supported CPU firmware. Confirm the actual rack and controller record before ordering.
What proves IC695ALG704-CB is ready after replacement?
Confirm module recognition, field-power status, the configured default behavior and a documented output check for every used channel.