Connects the supported RX3i CPU to its Energy Pack.
Product Identification
IC695CBL001 is the PACSystems RX3i connection cable used between the Energy Pack and supported CPE302/305/310-Bxxx controllers.
The manufacturer installation guide directs the cable from the connector on the bottom of the Energy Pack to the corresponding connector on the bottom of the CPU.
This part should not be treated as a general Ethernet, USB or backplane cable, and the guide does not list CPE330 in this cable instruction.
Engineering Data
| Manufacturer | Emerson |
|---|---|
| Exact model | IC695CBL001 |
| Product type | Energy Pack connection cable |
| Platform | PACSystems RX3i |
| Documented CPU families | CPE302-Bxxx, CPE305-Bxxx and CPE310-Bxxx |
| Energy Pack position | Mounted to the left of the module in rack slot 0 |
| Connection points | Bottom Energy Pack connector to bottom CPU connector |
| Installation reference | PACSystems RX3i CPE302/305/310-Bxxx installation guide GFK-3249C |
Functions
Provides the defined hardware path used during loss-of-power data preservation.
Uses keyed endpoints intended for the documented CPU and Energy Pack connection.
Keeps the cable identity traceable separately from the CPU and Energy Pack.
Applications
- CPE302-Bxxx installations using the documented Energy Pack arrangement.
- CPE305-Bxxx installations using the documented Energy Pack arrangement.
- CPE310-Bxxx installations using the documented Energy Pack arrangement.
- Controlled replacement of a damaged or missing Energy Pack interconnect.
Lifecycle
- Inspect both connectors, cable jacket, strain relief and routing before reuse.
- Do not pull on conductors or force a keyed connector during installation.
- After first power-up or long storage, allow the Energy Pack time to charge until CPU status is normal.
- Record the CPU and Energy Pack labels with the cable enquiry.
About IndustryParts
https://www.industryparts.com/Cable enquiries include both connected assemblies
IndustryParts handles IC695CBL001 with the CPU, Energy Pack and endpoint photographs needed to confirm the documented connection.
- CPU family confirmed
- Both endpoints photographed
- Routing and condition reviewed
FAQ
Is IC695CBL001 documented for IC695CPE330?
The cited CPE302/305/310-Bxxx installation guide documents IC695CBL001 for those CPU families; do not extend that compatibility to CPE330 without a separate manufacturer reference.
What labels should accompany an IC695CBL001 request?
Provide the CPU, Energy Pack and cable labels plus clear photographs of both connector ends and the installed routing.
Can IC695CBL001 be replaced by a similar-looking cable?
No. Use the documented Emerson cable identity and verify connector keying and supported hardware rather than matching appearance.
Why can the CPU status LED blink after installing IC695CBL001?
The manufacturer notes that a new or fully discharged Energy Pack may need several seconds to reach operating charge after power-up.
What should be inspected before the Energy Pack is returned to service?
Check both latches and connectors, cable strain relief, routing clearance, Energy Pack charge status and the CPU power-loss retention test.