Emerson IC695CPE302-BBAB RX3i Controller
A B-series CPE302 backplane controller with 2 MB user memory, two Gigabit Ethernet ports and firmware release 10.76.
Product Overview
IC695CPE302-BBAB is a PACSystems RX3i CPE302 B-series controller. It performs real-time machine and process control from the universal backplane and communicates with programming, HMI/SCADA and remote systems through embedded Ethernet and serial interfaces.
The BBAB release is identified with firmware 10.76 in the manufacturer release history. B-series hardware has a different platform and firmware boundary from earlier A-series controllers, so the complete suffix must remain in the replacement record.
Performance
- Executes control logic written in Ladder Diagram, Structured Text, Function Block Diagram or C.
- Supports secure OPC UA and PAC Security Center certificate management.
- Provides two internally switched Gigabit Ethernet ports for plant and programming communications.
- Uses an IC695ACC400 Energy Pack to save user memory to non-volatile storage during power loss.
Technical Details
| Manufacturer | Emerson |
|---|---|
| Model | IC695CPE302-BBAB |
| Product Family | PACSystems RX3i CPE302-Bxxx |
| Form Factor | RX3i backplane controller |
| User Memory | 2 MB |
| Non-Volatile Flash User Memory | 2 MB |
| Program Blocks | Up to 512; maximum 128 KB per block |
| Discrete I/O References | 32 kbits for %I and %Q |
| Analog I/O References | Up to 32K words each for %AI and %AQ |
| Ethernet | Two internally switched 10/100/1000 RJ45 ports |
| USB | USB 2.0 Type-A for removable data storage |
| Programming | Ladder, Structured Text, Function Block Diagram and C |
| Security / OPC | Encrypted OPC UA connections and certificate management support |
| Energy Pack | IC695ACC400 |
| Hardware Release | B-series; firmware is not compatible with earlier A-series hardware |
| BBAB Firmware Release | 10.76 (EKZY), November 2022 |
| Operating Temperature | 0 to 60 °C |
System Integration
- Use PAC Machine Edition and the correct target/firmware package for the B-series controller.
- Back up the full project, hardware configuration, passwords/certificates and Ethernet settings.
- Verify the Energy Pack, RTC battery, USB/RDSD media and every I/O/option module.
- Stage network, I/O and machine testing before releasing the replacement CPU to production.
Applications
- Real-time machine, process and material-handling control.
- RX3i systems requiring Gigabit Ethernet, OPC UA and modular backplane I/O.
- Replacement of the exact CPE302 B-series hardware and firmware generation.
FAQ
Why must IC695CPE302-BBAB not be replaced with an A-series CPE302 without review?
The B-series uses a new hardware platform and incompatible firmware boundary, so project, firmware, ports and migration procedure must be checked.
What project assets should be exported before changing IC695CPE302-BBAB?
Save the PAC Machine Edition project, hardware configuration, force tables, passwords/OEM keys, certificates, Ethernet settings, RDSD files and fault tables.
How should the two Ethernet ports on IC695CPE302-BBAB be evaluated?
They are an internal switch, so topology, loops, MRP design, IP addressing and external-switch behavior must be reviewed rather than treating them as two isolated interfaces.
What maintenance item is separate from the Energy Pack on IC695CPE302-BBAB?
The real-time-clock battery has its own replacement schedule; a healthy Energy Pack does not prevent clock reset after RTC-battery failure.
What acceptance test should follow an IC695CPE302-BBAB exchange?
Verify firmware and project checksum, I/O, Ethernet/serial protocols, OPC UA certificates, memory retention, clock, diagnostics, safety interlocks and controlled machine sequences.
Recommended Models
| 87.0634-014-NT-A6379/Pico/32-1/S1.6 | DPX3 | HWIC-1GE-SFP |
| OMAL D116H070 DN65/PN16 | Allen-Bradley 140MT-C3E | CM588-CN-XC 1SAP372800R0001 |
| Interlogix 80-632-3N-XT | MS 040-11rc-165 | DSBC-50-40-PPSA-N3 |
| CFQ-5251 | PELCO GIT100 | 56C315RP |
| k0002353M001 | MDX61B0110-5A3-4-0T/DEH11B/DFS21B | UK 432y-M20 |
| 3SK1111-1AB30 | Siemens 2KJ3990-0RU | MR 45-C2-1321-A-30.5-30.5-G1-V3 |
| EX270 | XP10BKB/DC | NGFW-300-4-R3B |
| PT 6-QUATTRO-PE | 354100 | E84AVTCE1834VX0-ETXXX |
| VL160N 3VL2706-1DC33-0AA0 | SNC-CH110 | NT 470 |
| 677 40D 01140 | 170PNT11020 170ADO35000 | UNDK 30U6112/S14 |