Home>DCS>HollySys HPWR01G DC Power Redundancy Distribution Module

Hot Categories

HollySys HPWR01G DC Power Redundancy Distribution Module

HollySys HPWR01G DC Power Redundancy Distribution Module

Item NO.: 3741489

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameHollySys HPWR01G DC Power Redundancy Distribution Module
  • Item NO.3741489
  • Weight0.4000 kg = 0.8818 lb = 14.1096 oz
  • CategoryDCS
  • BrandHollysys
  • Creation Time2026-08-19
  • HOLLiAS MACS-K · DCS
  • DC Power Redundancy Distribution Module
  • HOLLiAS MACS-K Series
HollySys HPWR01G | DC Power Redundancy Module

Key Information

HPWR01G is a DC power redundancy distribution module from HollySys, designed for the HOLLiAS MACS-K series distributed control system (DCS). It is used to achieve redundant power supply configuration for 24 VDC or 48 VDC systems, typically paired with HPW2405G, HPW2410G, or HPW2420G power supply modules .

The HPWR01G provides a fail‑over solution by combining two power inputs into a single regulated output. It also includes the necessary terminals for distribution to downstream modules and includes protection features such as reverse polarity protection and overcurrent protection .

The "G" suffix indicates the general industrial version, conforming to IEC/EN 62368‑1 and EMC immunity standards (EFT, ESD, Surge) .

Redundancy module 22–60 VDC input 20 A max MACS-K series G‑grade
Key details
  • DC power redundancy distribution
  • 22–60 VDC wide input range
  • 20 A max output current
  • HOLLiAS MACS‑K DCS compatible
  • Industrial G‑grade version

Functions

Redundancy & power distribution

  • Dual input redundancy — Combines two 24 VDC or 48 VDC power inputs (from HPW series power supplies) into a single regulated output. If one input fails, the other automatically takes over without interruption.
  • Power distribution — Provides multiple output terminals for distributing the redundant power to downstream modules, including controllers, I/O modules, and fieldbus segments.
  • Wide input range — Accepts 22–60 VDC input, making it compatible with both 24 VDC and 48 VDC power systems.

Protection & monitoring

  • Protection features — Integrated overcurrent protection, short‑circuit protection, and reverse polarity protection safeguard the module and connected loads .
  • Status indication — LED indicators provide immediate visual feedback on input status, output status, and fault conditions.
  • Wide temperature operation — Supports operation from -25°C to +70°C, suitable for outdoor cabinets and cold climates .

Specifications

Electrical specifications

Manufacturer HollySys 
Model HPWR01G
Product type DC power redundancy distribution module
Input voltage 22–60 VDC
Input current (max) 20 A (per input)
Output voltage Vin – 0.65 VDC (diode drop)
Output current (max) 20 A
Switching time ≤ 30 ms (typical)
Efficiency ≥ 95% (typical)
Protection Overcurrent, short‑circuit, reverse polarity, overtemperature
LED indicators Input status, output status, fault

Physical & environmental

Mounting DIN‑rail (EN 50022) or panel mounting
Operating temperature -25°C to +70°C (G‑grade)
Storage temperature -40°C to +85°C
Relative humidity 5% – 95% RH (non‑condensing)
Protection rating IP20
Approvals CE, UL, GB/T 18268 (EMC)
Certification IEC/EN 62368‑1
Terminals Screw‑type (2.5 mm² / 14 AWG)
Note: The HPWR01G is designed for use with HPW2405G, HPW2410G, or HPW2420G power supplies in a redundant configuration .

Installation

Proper installation of the HPWR01G redundancy module ensures reliable power availability for the DCS system.

Mounting & wiring guidelines

Mounting position DIN‑rail (EN 50022) inside control cabinet
Input connections Two DC power inputs (from HPW series power supplies)
Output connections Multiple output terminals for distribution to DCS modules
Wiring 2.5 mm² (14 AWG) stranded wire with ferrules
Grounding Connect ground terminal to cabinet ground
Ambient temperature Ensure adequate clearance for airflow, especially at high ambient temperatures
Input protection External fuses or circuit breakers recommended for each input
Installation notes:
  • Mount the HPWR01G on a standard DIN‑rail within the control cabinet. Ensure sufficient clearance for wiring and ventilation.
  • Connect the two DC power inputs to separate power supplies (e.g., HPW2410G or HPW2420G) to achieve true redundancy.
  • When using the HPWR01G in a HOLLiAS MACS‑K DCS system, it is typically installed in the power distribution section of the cabinet .
  • For outdoor or cold climate installations, the G‑grade variant supports operation down to -25°C .
  • Use only copper conductors rated for the operating temperature and current capacity.

Lifecycle

Active currently in production — fully supported

Product status: The HPWR01G remains an active, supported product in HollySys's HOLLiAS MACS-K DCS portfolio. It continues to be the recommended redundancy module for new MACS-K power distribution systems.

Spare parts & support: Replacement units and terminal blocks are available through HollySys's standard support channels and authorized distributors.

Replacement & migration:

Redundancy configuration: The HPWR01G is typically used in a 1+1 redundant configuration with two HPW series power supplies. For higher reliability, the module can be combined with a second HPWR01G in a fully redundant architecture .
  • When upgrading from older MACS‑K systems, ensure that the HPWR01G is compatible with the existing power supplies (HPW2405G/HPW2410G/HPW2420G).
  • For new installations, consider the G‑grade version for extended temperature range applications.
  • The HPWR01G is not designed for generic commercial electronics — it is specifically engineered for DCS/PLC power distribution .

Recommendation: For new HOLLiAS MACS‑K DCS installations, the HPWR01G remains the recommended power redundancy solution.