A multifunction Series C module for qualified speed measurement and local protection action.
CC-PSP401 conditions turbine speed signals, evaluates protection limits and coordinates local trip action with the Series C control environment. Its supporting general I/O serves the same turbomachinery protection application.
| Parameter | Official specification |
|---|---|
| Speed inputs | 4 active or passive probes |
| Voting | Onboard two-out-of-three speed voting |
| Analog inputs | 8 channels; 0-5 V, 1-5 V, 0.4-2 V or 4-20 mA through 250 ohms |
| Analog output | 1 channel, 4-20 mA, maximum 760-ohm load |
| Digital inputs | 8 channels, configurable as trip inputs |
| Digital outputs | 4 isolated Form A/B outputs |
| Overall input-to-trip latency | 40 ms or less |
| Speed / analog processing | 2.5 ms / 10 ms |
| Passive speed probe | 0.5 V peak minimum, below 42 V peak, 150 Hz-25 kHz |
| Active TTL probe | OFF below 1 V, ON above 3.5 V, 1 Hz-10 kHz |
| Active 24 V probe | OFF below 6 V, ON above 10 V, 1 Hz-10 kHz |
| Digital-output rating | 0.5 A at 230 VAC or 2 A at 24 VDC |
| Analog-input accuracy | ±0.075% FS at 23.5±2°C; ±0.15% from 0 to 60°C |
| IOTA | CC-TSP411 redundant 18-inch |
| Component | Integration role |
|---|---|
| CC-TSP411 | Provides the matching field termination and module mounting arrangement |
| C300 controller | Uses the qualified speed value for regulation and supervisory functions |
| Overspeed trip circuit | Receives the locally evaluated protection action |
| Experion engineering database | Holds the approved module configuration and diagnostics |
Confirm firmware, control strategy, terminal assignment, probe excitation and trip-relay wiring before replacement. Validate the complete protection loop after installation.
| Question | Answer |
|---|---|
| Can a general-purpose I/O module replace it? | No. Use the approved Speed Protection Module configuration. |
| Where should trip settings be verified? | In the approved project configuration and protection documentation. |
| What diagnostics require review? | Review probe health, wiring status, channel qualification and output feedback. |
| What is required after installation? | Complete the approved functional and overspeed protection tests. |
The following models are available for sourcing inquiries. Contact us with the exact part number and required quantity.
| No. | Recommended Model | No. | Recommended Model | No. | Recommended Model |
|---|---|---|---|---|---|
| 1 | HFRC-01C | 11 | IR425 / ir425-D4-2 | 21 | s4C751104 |
| 2 | 7PCBS3001 - CML-596 | 12 | SEC-TEA-230-5045 | 22 | 5WG1 372-5EY01 |
| 3 | AC010S | 13 | SB-DN-PS750 | 23 | LQSE-4S5-230-D |
| 4 | sg001043 | 14 | CM485 | 24 | RP128KCLPILA |
| 5 | K-EF234L03E | 15 | 3718B004 | 25 | H3-5068X03 |
| 6 | ADCDW2506TU | 16 | FX03 / LP-FX03A11-0C | 26 | SB-RLY12C10A-DN |
| 7 | ABB 2CDG110042R0011 | 17 | ABB 1MRK 000 863-AN | 27 | SCB-5003P 1280H |
| 8 | K01-0958 | 18 | RPM10-NIST | 28 | APIN0305 |
| 9 | TB-C | 19 | MF6FTJ0026 | 29 | ACC2 |
| 10 | GE 3000 | 20 | SNZ4052K | 30 | VS1504 Cat5 |