Home>PLC>Pepperl+Fuchs 098916 One-Channel Field-Mount Surge Protection Barrier

Hot Categories

Pepperl+Fuchs 098916 One-Channel Field-Mount Surge Protection Barrier

Pepperl+Fuchs 098916 One-Channel Field-Mount Surge Protection Barrier

Item NO.: 3806691

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NamePepperl+Fuchs 098916 One-Channel Field-Mount Surge Protection Barrier
  • Item NO.3806691
  • Weight0.2000 kg = 0.4409 lb = 7.0548 oz
  • CategoryPLC
  • Brandothers
  • Creation Time2026-10-23
FS-LB-I · ONE SIGNAL LINE · M20 × 1.5 FIELD MOUNT

Pepperl+Fuchs 098916 One-Channel Field-Mount Surge Protection Barrier

The Pepperl+Fuchs catalog number for an FS-LB-I stainless-steel surge barrier used at a field-device entry.

Protected lines1
Discharge current20 kA total
Ingress protectionIP67
01
PRODUCT RECORD

Overview

Pepperl+Fuchs 098916 identifies the FS-LB-I one-channel surge protection barrier. It is a screw-in field module for protecting the signal connection of a field device.

The stainless-steel body uses an M20 × 1.5 mounting thread. Manufacturer data lists a 20 kA total discharge current for an 8/20 µs impulse, at least 500 V isolation from earth and suitability for hazardous-area applications.

The exact catalog number matters because the FS-LB-I mechanical thread differs from the NPT and PG variants in the same protection family.

02
MANUFACTURER DATA

Specifications

Manufacturer
Pepperl+Fuchs
Exact catalog number
098916
Product designation
FS-LB-I
Protected signal lines
1
Mounting
M20 × 1.5 thread
Housing
Stainless steel 1.4401 / AISI 316
Degree of protection
IP67
Rated voltage
48 V maximum
Rated current
250 mA maximum
Ground isolation
500 V breakdown voltage minimum
Total discharge current
20 kA, 8/20 µs
Common-mode surge current
10 kA line to ground
Differential surge current
5 kA line to line
Ambient temperature
−30 to 60 °C
Cable length
0.3 m
Functional safety
Up to SIL 3 according to IEC/EN 61508
03
ENGINEERING CHARACTER

Features

A

Field-entry protection

The screw-in enclosure places surge protection close to the connected instrument rather than only inside the cabinet.

B

Hazardous-area capability

The manufacturer provides the relevant Ex marking and certificate references for the approved installation.

C

Fast transient response

Published nominal response is 1 ns symmetrical and 100 ns asymmetrical.

D

Distinct mechanical code

The M20 thread is part of the FS-LB-I identity and should not be substituted with another F-series thread form.

04
APPLICATION FIT

Applications

FIELD CONTEXT

Field transmitter protection

Protecting one field signal line where the instrument enclosure provides the matching M20 entry.

FIELD CONTEXT

Ex-area instrument loops

Using the barrier within the limits and installation conditions of its hazardous-area approvals.

FIELD CONTEXT

Outdoor junction points

Applying the stainless-steel IP67 field-mount housing in a properly sealed installation.

05
SERVICE DISCIPLINE

Lifecycle

RECORD

Record the mechanical entry

Capture 098916, FS-LB-I marking, thread size, enclosure entry and loop drawing.

MATCH

Inspect the surge path

Check bonding, cable routing, enclosure sealing and the condition of the stainless-steel body before return to service.

PROVE

Verify loop integrity

Confirm insulation, continuity, signal quality and the applicable hazardous-area checks after installation.

CONTROLLED INDUSTRIAL SUPPLY

About IndustryParts

https://www.industryparts.com/

Application evidence stays with 098916

IndustryParts keeps the requested model, quantity, label evidence and delivery record together so the proposed supply can be reviewed against the real installed application before dispatch.

Exact label recorded
System evidence reviewed
Dispatch identity retained
IndustryParts industrial automation support
06
BUYER SUPPORT

FAQ

Q01

What should accompany a 098916 quotation request?

Send the FS-LB-I label, loop voltage and current, field-device type, M20 entry detail, hazardous-area classification and quantity.

Q02

Is 098916 the NPT-thread version of this barrier?

No. Pepperl+Fuchs identifies FS-LB-I as the M20 × 1.5 version; the FN-LB-I uses a 1/2-inch NPT mounting thread.

Q03

Which surge ratings belong to 098916?

The published values are 20 kA total discharge current, 10 kA line-to-ground and 5 kA line-to-line for the stated impulse conditions.

Q04

What enclosure evidence matters when replacing 098916?

Confirm the M20 entry, thread engagement, seal arrangement, bonding path, ingress protection and hazardous-area installation requirements.

Q05

How should 098916 be accepted after installation?

Inspect the mounted seal and bonding, then verify loop continuity, insulation, stable signal transmission and all site-required Ex checks.

ENQUIRY INFORMATION

Send the complete 098916 label, requested quantity and delivery destination.