Rittal SK 3110.000 Enclosure Internal Thermostat
01Product Identification
Rittal SK 3110.000 is an enclosure internal thermostat for controlling fans, heaters, and heat exchangers or for providing a temperature-monitoring signal. It uses a bimetal controller with thermal feedback and a single-pole change-over quick-break contact in a compact RAL 7035 enclosure.
02Engineering Data
| Manufacturer | Rittal |
|---|---|
| Model | SK 3110.000 |
| Product Type | Enclosure internal thermostat |
| Temperature Range | 5...60 deg C |
| Sensor Element | Bimetal controller with thermal feedback |
| Contact | Single-pole change-over quick-break contact |
| Heating Contact Load | AC 10 (4) A, inductive at cos phi 0.6 |
| Cooling Contact Load | AC 5 (4) A, inductive at cos phi 0.6 |
| DC Contact Load | Maximum 30 W |
| Switching Difference | Approximately 1 K +/-0.8 K |
| Rated Operating Voltage | 24...230 V AC, 1-phase; 24...60 V DC |
| Mounting | 35 mm support rail or supplied snap-mount adaptor |
| Color | RAL 7035 |
| Pack Quantity | 1 piece |
03Functions
Operating Functions
- Controls enclosure cooling or heating equipment through a change-over contact.
- Can also be wired as a signal generator for enclosure temperature monitoring.
- External screw-terminal access supports time-saving field connection.
- The supplied adaptor supports snap mounting on an enclosure section or mounting plate.
- The unit can be mounted vertically or horizontally on a 35 mm rail.
- Compact dimensions suit typical industrial enclosure climate-control layouts.
Product Identity
Manufacturer: Rittal
Model: SK 3110.000
Product Type: Enclosure Internal Thermostat
04System Integration
- Select the heating or cooling contact path according to the controlled device and wiring diagram.
- Keep the connected fan, heater, heat exchanger, contactor, or signal circuit within the documented contact load.
- Confirm the available AC or DC control voltage and the required switching direction.
- Mount the thermostat where enclosure air represents the temperature to be controlled, away from misleading local heat sources.
- The optional SK 3110.200 bottom-mounted adaptor is listed for SK 3110.000 and SK 3118.000 when targeted cable entry is required.
05Applications
- Fan-and-filter unit control in industrial enclosures.
- Enclosure heater control for low-temperature or condensation management.
- Heat-exchanger enable control.
- Temperature alarm or monitoring signal generation in control panels.
06Lifecycle
- Record the setpoint, contact wiring, conductor identification, mounting orientation, and controlled device before removal.
- Isolate the control circuit and verify absence of voltage before opening terminals.
- Reproduce the change-over contact logic so heating or cooling acts in the intended direction.
- After installation, test the switching response around the setpoint and verify the controlled device current.
- Check enclosure airflow and sensor location if the new thermostat cycles too early or too late.
FAQFrequently Asked Questions
What temperature range can be set?
The setting range is 5 to 60 degrees Celsius.
Can the thermostat control both heating and cooling?
Yes. The change-over contact provides documented contact ratings for heating and cooling circuits.
How is it mounted?
It mounts on a 35 mm rail or uses the supplied adaptor for snap fastening in an enclosure section or on a mounting plate.
What is the switching difference?
Rittal specifies approximately 1 K with a tolerance of plus or minus 0.8 K.
Can it be used only for direct load control?
No. Rittal also identifies it as a signal generator for monitoring enclosure internal temperature.
What should be tested after replacement?
Verify the setpoint, heating or cooling contact logic, connected load, switching response, and actual enclosure temperature behavior.
+Recommended Models
| TK_C21P RTU A01P | ABB 6197/52-101-500 | 024-30935-000 |
| Nov-33 | eZNS-T100-NB-R-047-WWG | ABL8RPS24100 |
| R134a,067N5157 | 3RU2116-0HB0 | ABB 1SDAO13856R1 |
| INJ-24-T | NJS8477EN | ATSU01N222LT |
| ABB 1SAP240000R0001 DI524 | MMS-A-350 | 2CDG 110095 R0011 |
| MTL4546Y | 3AA01318700 | 30.640.1 |
| LNL-1320 DOC-600-R14104 | EP1Z01IPHO | 9470-26-904-102 |
| RPM10-NIST | SC90AF021 | CPU6 3BA23197BAED |
| MT1963-1002 | EMC2 API4SG10 071-000-521 | 400:0.1 7801C40G03 |
| ABB 2CDG 110 044 R0011 | BZMC2-A200 | EKI-2725FI-AE |