Home>PLC>Siemens 6ES7231-4HD32-0XB0 SM 1231 4-Channel Analog Input Module

Hot Categories

Siemens 6ES7231-4HD32-0XB0 SM 1231 4-Channel Analog Input Module

Siemens 6ES7231-4HD32-0XB0 SM 1231 4-Channel Analog Input Module

Item NO.: 3810426

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameSiemens 6ES7231-4HD32-0XB0 SM 1231 4-Channel Analog Input Module
  • Item NO.3810426
  • Weight0.1400 kg = 0.3086 lb = 4.9384 oz
  • CategoryPLC
  • BrandSiemens
  • Creation Time2026-10-27
SIMATIC S7-1200TECHNICAL PRODUCT RECORD
SM 1231 · FOUR DIFFERENTIAL INPUTS · VOLTAGE OR CURRENT

Siemens 6ES7231-4HD32-0XB0 SM 1231 4-Channel Analog Input Module

A four-channel S7-1200 analog input module for documented voltage and current signals.

Input count4 differential
Resolution12 bit + sign
Maximum update625 µs, all channels
01
PRODUCT DOSSIER

Key Information

6ES7231-4HD32-0XB0 is the SIMATIC S7-1200 SM 1231 module with four differential analog inputs. Siemens permits voltage ranges of ±10 V, ±5 V and ±2.5 V plus 0–20 mA and 4–20 mA current ranges.

The module is intended for voltage or current acquisition; it is not the RTD or thermocouple execution. Channel mode, scaling, conductor routing and the complete MLFB must stay with the PLC hardware record.

Siemens publishes a 24 V DC rated supply, 1.5 W typical power loss and a maximum 625 µs update for all four channels.

02
OPERATING ROLE

Functions

A

Mixed analog acquisition

Accepts four differential voltage or current signals in the ranges enabled by the hardware configuration.

B

Process-value conversion

Converts each selected range at up to 12-bit resolution plus sign for transfer to the S7-1200 CPU.

C

Channel diagnostics

Supports a controlled commissioning record built around wiring, configured range and plausible raw values.

D

Compact expansion

Adds four analog points without selecting the higher-density eight-channel 4HF32 module.

03
MANUFACTURER DATA

Specifications

Manufacturer
Siemens
Exact model
6ES7231-4HD32-0XB0
Module designation
SM 1231 AI 4x13 bit
Analog inputs
4 differential
Voltage ranges
±10 V, ±5 V, ±2.5 V
Current ranges
0–20 mA, 4–20 mA
Resolution
12 bit + sign
All-channel update
625 µs maximum
Rated supply
24 V DC
Typical power loss
1.5 W
Current input resistance
280 Ω
Voltage input resistance
≥9 MΩ
IndustryParts industrial automation supply support
DOCUMENTED INDUSTRIAL SUPPLY

About IndustryParts

https://www.industryparts.com/

Exact-model handling for 6ES7231-4HD32-0XB0

IndustryParts keeps the complete model label, requested quantity, application evidence and delivery requirements together so the proposed supply can be checked against the installed system before dispatch.

04
CONTROLLED WORK

Installation

Define every channel mode

Record voltage or current selection, range, scaling, signal common and shield treatment before removal.

Respect input boundaries

Check source polarity and ensure field fault conditions remain within the published 35 V and 40 mA destruction limits.

Prove raw and scaled values

Apply traceable test points to each used channel and compare PLC counts, engineering units and alarm behavior.

05
SERVICE RECORD

Lifecycle

Configuration control

Keep the TIA Portal hardware record and complete 6ES7231-4HD32-0XB0 MLFB together.

Calibration evidence

Archive the source instrument, applied points, tolerance and as-left readings for each active loop.

Spare distinction

Do not substitute the eight-channel 4HF32 or sensor-specific RTD/TC variants without engineering review.

07
CUSTOMER QUESTIONS

FAQ

Q01

Which channel record should accompany a 6ES7231-4HD32-0XB0 enquiry?

Provide the CPU MLFB, installed slot, configured range for every channel, loop drawings, project version and full module label.

Q02

Can 6ES7231-4HD32-0XB0 directly measure an RTD or thermocouple?

No. Siemens identifies this article for voltage and current input; use the specified RTD or TC module when those sensors are required.

Q03

Why is 4HD32 not interchangeable with 4HF32 for 6ES7231-4HD32-0XB0?

The 4HD32 has four inputs while 4HF32 has eight; terminal allocation, project data and channel density differ.

Q04

What should be captured before removing 6ES7231-4HD32-0XB0?

Save scaling, filter settings, diagnostic state, conductor markers and stable reference readings for every active input.

Q05

How is 6ES7231-4HD32-0XB0 accepted after installation?

Verify each configured range with known signals, confirm engineering scaling and complete the approved alarm and interlock tests.