Home>PLC>Siemens 6ES7288-2DR16-0AA0 SIMATIC S7-200 SMART SM DR16 Digital I/O Module

Hot Categories

Siemens 6ES7288-2DR16-0AA0 SIMATIC S7-200 SMART SM DR16 Digital I/O Module

Siemens 6ES7288-2DR16-0AA0 SIMATIC S7-200 SMART SM DR16 Digital I/O Module

Item NO.: 3802838

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameSiemens 6ES7288-2DR16-0AA0 SIMATIC S7-200 SMART SM DR16 Digital I/O Module
  • Item NO.3802838
  • Weight1.0000 kg = 2.2046 lb = 35.2740 oz
  • CategoryPLC
  • BrandSiemens
  • Creation Time2026-10-21
SIMATIC S7-200 SMART expansion I/O | exact catalog identity

Siemens 6ES7288-2DR16-0AA0 SIMATIC S7-200 SMART SM DR16 Digital I/O Module

Eight 24 V DC inputs and eight 2 A relay outputs for mixed-voltage load interfacing.

Module Profile

Siemens 6ES7288-2DR16-0AA0 is a SIMATIC S7-200 SMART SM DR16 Digital I/O Module identified by the complete submitted catalog string. The suffix and revision characters remain part of the supply identity.

Selection of 6ES7288-2DR16-0AA0 should follow the installed label, rack or controller record, field wiring and the verified technical details below; a neighboring family number is not treated as interchangeable.

Published Data

Manufacturer
Siemens
Exact model
6ES7288-2DR16-0AA0
Module designation
SM DR16
Digital inputs
8
Input type
24 V DC, sink/source
Digital outputs
8 relay outputs
Relay output rating
2 A under published load limits
Output technology
Electromechanical relay contacts

System Role

The module combines eight 24 V DC inputs with eight electromechanical relay outputs.

Relay contacts support approved load circuits that cannot be connected directly to a sourcing transistor output.

The DR16 wiring diagram defines input commons and the relay field-feed arrangement.

The full ordering number keeps the relay module distinct from DT16 and the higher-density DR32.

Integration Checks

  • Archive the project and record all input commons, relay feeds, load voltages and point assignments.
  • Inspect contact loads for steady current, inrush and approved suppression.
  • Keep AC and DC circuit separation and conductor routing consistent with the panel design.
  • Test all inputs, relay contacts, feedback signals and machine interlocks after installation.

Use Cases

  • S7-200 SMART panels with mixed input monitoring and relay-switched field loads.
  • Applications requiring contact isolation between the controller logic and approved load circuits.
  • Like-for-like replacement of a documented SM DR16 expansion position.

FAQ

Q01Can 6ES7288-2DR16-0AA0 be replaced by 6ES7288-2DT16-0AA0?

Not directly. DR16 uses relay contacts, while DT16 uses sourcing transistor outputs with different load and supply requirements.

Q02What should be recorded for each 6ES7288-2DR16-0AA0 relay output?

Record load voltage, steady and inrush current, switching frequency, suppression and the terminal/feed arrangement.

Q03Does DR16 mean sixteen relay outputs on 6ES7288-2DR16-0AA0?

No. It identifies sixteen mixed points: eight digital inputs and eight relay outputs.

Q04What panel checks matter before installing 6ES7288-2DR16-0AA0?

Verify conductor segregation, branch protection, terminal tightness and the documented relay supply feeds.

Q05How should 6ES7288-2DR16-0AA0 be accepted after replacement?

Exercise every input and relay output under controlled conditions, verify feedback and prove the complete interlock sequence.