Siemens 6ES7516-3AN01-0AB0 SIMATIC S7-1500 CPU 1516-3 PN/DP
01Technical Summary
Siemens 6ES7516-3AN01-0AB0 is a SIMATIC S7-1500 CPU 1516-3 PN/DP central processing unit with 1 MB program work memory and 5 MB data work memory. Its integrated communications comprise a PROFINET IRT interface with a two-port switch, a second PROFINET RT interface and a PROFIBUS interface. The CPU requires a SIMATIC Memory Card and is identified by Siemens as a cancelled spare-part article, so both the installed hardware generation and the officially named successor must be reviewed before a change is approved.
02Specifications
| Manufacturer | Siemens |
|---|---|
| Article Number | 6ES7516-3AN01-0AB0 |
| Product Designation | CPU 1516-3 PN/DP |
| Automation Platform | SIMATIC S7-1500 |
| Program Work Memory | 1 MB |
| Data Work Memory | 5 MB |
| Load Memory | SIMATIC Memory Card, maximum 32 GB |
| Bit Processing Time, Typical | 10 ns |
| Interface 1 | PROFINET IRT with integrated 2-port switch |
| Interface 2 | PROFINET RT |
| Interface 3 | PROFIBUS |
| Rated Supply | 24 V DC; permissible range 19.2 to 28.8 V DC |
| Firmware / Engineering | V2.9; TIA Portal V17 for FW V2.9 |
| Display | 6.1 cm diagonal |
| Operating Temperature | 0 to 60 °C horizontal; 0 to 40 °C vertical |
03Features
Key Functions
- Executes S7-1500 control logic with a typical bit-operation time of 10 ns.
- Separates program and data work memory into 1 MB and 5 MB capacities.
- Provides deterministic PROFINET IRT connectivity through an integrated two-port switch.
- Adds a second PROFINET RT interface for another Ethernet communication path.
- Includes an integrated PROFIBUS interface for established distributed automation networks.
- Supports I&M data, configuration control by data set and isochronous operation in supported configurations.
Identification
- Manufacturer: Siemens
- Model: 6ES7516-3AN01-0AB0
- Product Type: SIMATIC S7-1500 CPU 1516-3 PN/DP central processing unit
- Status: Spare part; cancelled product
04Compatibility
- Confirm the complete article number and hardware functional status before exchanging an installed CPU.
- A SIMATIC Memory Card is mandatory; transfer the project only after verifying card capacity, firmware and protection settings.
- Match the existing PROFINET IRT topology, device names, IP configuration, update times and the second PROFINET network.
- Verify PROFIBUS address, baud rate, bus termination, device configuration and diagnostic organization.
- TIA Portal support depends on the installed firmware; Siemens lists V17 for firmware V2.9 and earlier integration paths for older firmware.
- Preserve the hardware configuration, user program, technology objects, communication relationships and retentive-data plan before replacement.
05Replacement
- Siemens identifies this article as a cancelled spare-part product with cancellation effective 2 June 2020.
- Siemens names 6ES7516-3AP03-0AB0 as the successor product; it is not a drop-in assumption because memory, performance and firmware differ.
- Compare work memory, CPU performance, interface behavior, firmware, TIA Portal version and all approvals before migration.
- Back up the project and record device names, IP parameters, PROFIBUS settings, certificates, passwords and Memory Card details.
- After installation, commission every communication path, distributed I/O station, safety-independent interlock and process sequence under controlled conditions.
06FAQ
What is Siemens 6ES7516-3AN01-0AB0?
It is a SIMATIC S7-1500 CPU 1516-3 PN/DP central processing unit with PROFINET and PROFIBUS interfaces.
How much work memory is integrated?
The CPU provides 1 MB for the program and 5 MB for data.
Is a SIMATIC Memory Card required?
Yes. Siemens specifies one SIMATIC Memory Card as mandatory, with supported load-memory capacity up to 32 GB.
Which industrial networks are integrated?
The CPU has PROFINET IRT with a two-port switch, a second PROFINET RT interface and one PROFIBUS interface.
What successor does Siemens identify?
Siemens identifies 6ES7516-3AP03-0AB0 as the successor, subject to a complete engineering comparison.
What should be verified after replacement?
Verify the project, firmware, Memory Card, all PROFINET and PROFIBUS communications, diagnostics, retentive data and the complete machine sequence.
+Recommended Models
| 115UM/1.5-4.5MILS | M1032-61635 B-M1032-94335-I | WS-2 02738C2 |
| 676102.0 Dzl,AEG A512 | X13760335-01 | 5504RV20P |
| CM7031 | ROYALTEC | TM3AI8 |
| ABB 1SAP112100R0270 TB521-ETH | 787-601 | 75314021 |
| 1AC/24VDC-20A-DN4014 | M2150-4DBC | HWP-D-108 |
| IM10 | MIL-RC3412 10/100BASE-TX | A12-SPC-LU-R ASCEND-12 |
| Allen Bradley 2711P-RDT7C /C | HTS-16T | DT3020 |
| 2CDG 110 093 R0011 | PQ3541 | MFM 3430 |
| TM3DI8 | TLU500 | 6SL3255-0AA00-4BA1 |
| LG-003552 | 1746-IB32 SLC500 | RSN4004 |