Siemens 6RY1707-0AA08 Parallel Connection Cable
A Siemens 5 m shielded patch cable used for parallel connections between SIMOREG DC-MASTER or SINAMICS DCM devices.
Key Information
6RY1707-0AA08 is the Siemens parallel-connection cable for SIMOREG DC-MASTER 6RA70 and SINAMICS DCM equipment. Siemens specifies an 8-core shielded UTP CAT5 patch cable wired in accordance with ANSI/EIA/TIA 568.
The cable connects the parallel interface between devices. A chain of n converters requires n−1 cables, while the first and last devices require the documented bus termination.
The lead must be a straight-through patch cable with both ends wired to the same TIA568 scheme. A crossover cable is not suitable for this interface.
Functions
Parallel-drive communication
Carries the documented inter-device connection used when compatible DC drives operate in parallel.
Daisy-chain continuity
Links X165 and X166 paths so the parallel interface can continue from one device to the next.
Shielded data path
Uses shielded CAT5 construction for the drive communication environment.
Service-ready length
Provides the Siemens standard cable length for controlled cabinet or lineup routing.
Specifications
| Manufacturer | Siemens | Exact model | 6RY1707-0AA08 |
|---|---|---|---|
| Product designation | Parallel connection cable | Compatible platforms | SIMOREG DC-MASTER 6RA70 / SINAMICS DCM |
| Cable standard | UTP CAT5 to ANSI/EIA/TIA 568 | Conductors | 8-core, shielded |
| Approximate length | 5 m | Required wiring | Straight-through; both ends to the same TIA568 scheme |
| Unsuitable wiring | Crossover cable | Quantity rule | n devices require n−1 cables |
About IndustryParts
https://www.industryparts.com/Parallel cables stay linked to the drive-chain map
IndustryParts records the cable article, device count, station order and requested quantity before a parallel-drive proposal is prepared.
- Exact submitted model retained
- Installed-system evidence reviewed
- Quotation identity kept traceable
Installation
Plan the chain
Record master and slave devices, station addresses, X165/X166 routing and the required number of cables.
Check end termination
Enable the documented bus termination only at the two physical ends of the parallel interface.
Commission in sequence
Assign unique station addresses before activating the parallel interface, then verify stable communication and drive roles.
Lifecycle
Connector care
Inspect latch retention, shield continuity and routing away from damage or excessive bend.
Parameter custody
Retain parallel-interface addresses, master/slave roles and termination settings with the drive project.
Cable identity
Keep the Siemens article and length visible so a generic crossover or unshielded lead is not introduced.
Related Models
FAQ
Is any CAT5 cable an acceptable substitute for 6RY1707-0AA08?
No. The connection must be shielded, straight-through and wired consistently to TIA568 at both ends; a crossover cable is unsuitable.
How many 6RY1707-0AA08 cables are required for four parallel devices?
A four-device chain requires three inter-device cables, with bus termination applied at the two physical ends.
What should be configured before enabling the interface linked by 6RY1707-0AA08?
Assign a unique station address to every device, define master and slave roles, and verify end termination.
Which connectors are associated with 6RY1707-0AA08 on SINAMICS DCM?
Siemens documents the parallel interface on the X165 and X166 connectors of the Control Unit.
What acceptance evidence belongs with 6RY1707-0AA08?
Record cable identity, shield and latch condition, device order, addresses, termination state and stable parallel communication.
Send the complete 6RY1707-0AA08 identity
Include requested quantity, destination and the installed-system evidence needed for compatibility review.