Home>PLC>Siemens 6SE6440-2UC24-0CA1 MICROMASTER 440 4 kW Inverter

Hot Categories

Siemens 6SE6440-2UC24-0CA1 MICROMASTER 440 4 kW Inverter

Siemens 6SE6440-2UC24-0CA1 MICROMASTER 440 4 kW Inverter

Item NO.: 3748265

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameSiemens 6SE6440-2UC24-0CA1 MICROMASTER 440 4 kW Inverter
  • Item NO.3748265
  • Weight5.5000 kg = 12.1254 lb = 194.0068 oz
  • CategoryPLC
  • BrandSiemens
  • Creation Time2026-08-27
  • MICROMASTER 440 4 kW Inverter
Siemens 6SE6440-2UC24-0CA1 MICROMASTER 440 4 kW Inverter

Siemens 6SE6440-2UC24-0CA1 MICROMASTER 440 4 kW Inverter

Unfiltered 200-240 V AC drive rated for 4 kW high-overload and 5.5 kW low-overload service.

ManufacturerSiemensModel6SE6440-2UC24-0CA1Product TypeMICROMASTER 440 variable-frequency drive without integrated filter

01Technical Summary

Siemens 6SE6440-2UC24-0CA1 is the unfiltered 200 to 240 V three-phase version of the MICROMASTER 440 drive in the 4 kW high-overload class. It supports a 5.5 kW low-overload rating and provides configurable digital, relay and analog channels plus a motor-temperature input. Because this article has no integrated EMC filter, the external EMC design and exact installed option set are important selection boundaries.

Configuration ControlVerify the full article number, installed hardware, electrical design, interfaces, wiring, software and lifecycle requirement before ordering.

02Specifications

Manufacturer Siemens
Article Number 6SE6440-2UC24-0CA1
Product Family MICROMASTER 440
Input Supply 200 to 240 V AC, 3-phase, ±10%
Input Frequency 47 to 63 Hz
Integrated Filter None
High-Overload Rating 4 kW / 5 hp
Low-Overload Rating 5.5 kW / 7.5 hp
Output Current 17.5 A high overload; 22.0 A low overload
Input Current 19.7 A high overload; 28.3 A low overload
Pulse Frequency 16 kHz
Control I/O 6 digital inputs, 3 relay outputs, 2 analog inputs, 2 analog outputs
Motor Sensor Input PTC / KTY input
Protection IP20

03Features

Key Functions

  • Unfiltered power-stage configuration for installations with separately engineered EMC measures.
  • Provides distinct 4 kW high-overload and 5.5 kW low-overload ratings.
  • Uses a documented 16 kHz pulse-frequency setting for this article data.
  • Integrates flexible digital, relay and analog I/O for control and monitoring.
  • Accepts PTC or KTY motor-temperature sensing.
  • Supports the control and parameterization functions of the MICROMASTER 440 platform.

Identification

  • Manufacturer: Siemens
  • Model: 6SE6440-2UC24-0CA1
  • Product Type: MICROMASTER 440 variable-frequency drive without integrated filter
  • Status: Cancelled product; spare part

04Compatibility

  • Use on a 200 to 240 V three-phase network and verify input protection and conductor sizing.
  • Provide the external filtering, line reactor and EMC measures required by the complete installation.
  • Match high-overload or low-overload current to the actual motor and load profile.
  • Confirm terminals, frame size, airflow, braking hardware, operator panel and communication option.
  • Restore only a verified parameter set for the exact machine and motor.
  • Check shielding, grounding, cable routing and motor-cable length during commissioning.

05Replacement

  • Siemens records the article as cancelled from 1 October 2019 and classifies it as a spare part.
  • The Siemens migration reference is SIOS entry 109746454.
  • Do not interchange filtered and unfiltered articles without reviewing the complete EMC design.
  • Document motor data, I/O, protection, communication settings and every parameter before removal.
  • Validate current, acceleration, deceleration, torque response, thermal protection, fieldbus control and machine safety after exchange.

06FAQ

Is 6SE6440-2UC24-0CA1 supplied with an integrated line filter?

No. Siemens identifies this exact version as a drive without an integrated filter.

What supply range is specified for this converter?

The input is 200 to 240 V AC, three phase, with a ±10% tolerance and 47 to 63 Hz frequency.

Which power levels correspond to its two duty classes?

It is rated at 4 kW for high-overload duty and 5.5 kW for low-overload duty.

What currents should be considered during selection?

The official data lists 17.5 A and 22.0 A output currents, with 19.7 A and 28.3 A input currents for the respective duty classes.

How large is the unfiltered 4 kW frame?

The published dimensions are 185 x 245 x 195 mm and the net weight is 5.5 kg.

What is the main replacement risk for this version?

A filtered drive should not be assumed equivalent; the external EMC components, cabling and installation design must be checked.