Limits inrush while the Basic Line Module DC link is precharged.
Product Profile
6SL3000-0KH14-0AA0 is a Siemens SINAMICS S spare-part pre-charging resistor rated at 4.0 ohms for the documented Basic Line Module precharge circuit.
Siemens specifies the resistor for 3 AC 500–690 V service, 47–63 Hz, with a pulse-energy limit of 18,000 Ws and a minimum interval of three minutes between precharge pulses.
The resistor becomes hot during operation. Enclosure ventilation, clearance, conductor sizing and protection must follow the SINAMICS installation manual.
Technical Data
| Manufacturer | Siemens |
|---|---|
| Exact order number | 6SL3000-0KH14-0AA0 |
| Product family | SINAMICS S spare part |
| Product type | Pre-charging resistor |
| Resistance | 4.0 Ω ±10% |
| Rated voltage | 690 VAC |
| Applicable supply range | 3 AC 500 to 690 V |
| Frequency | 47 to 63 Hz |
| Pulse energy | 18,000 Ws |
| Minimum pulse interval | 3 minutes |
| Precharge current | 86 A with one resistor per phase; 172 A with two parallel resistors per phase |
| Ambient temperature basis | 60 °C |
| Conductor cross-section | 2.5 mm² |
| Country of origin | Denmark |
System Role
Operates for a short controlled pulse rather than continuous power dissipation.
Forms part of the line-side precharge and switching sequence.
Protects the connected power electronics when correctly coordinated with the contactor logic.
About IndustryParts
https://www.industryparts.com/Pulse duty and line-module identity stay visible
IndustryParts prepares 6SL3000-0KH14-0AA0 quotations with the exact Basic Line Module and resistor arrangement.
- 4.0-ohm value retained
- Pulse interval reviewed
- Line-module MLFB requested
Compatibility
- Use only in the Basic Line Module arrangement documented for this resistor.
- Confirm supply voltage, line-module frame and the required number of resistors per phase.
- Maintain the specified pulse interval and conductor size.
- Provide ventilation and clearance for the hot resistor body.
Applications
- SINAMICS S Basic Line Module precharge circuits in the documented 500–690 V range.
- Replacement of a damaged 4.0-ohm precharging resistor with the exact Siemens order number.
- Drive-cabinet service where inrush control and contactor timing are verified.
FAQ
Q01Can 6SL3000-0KH14-0AA0 be energized continuously?
No. It is a pulse-duty precharging resistor. The documented 18,000 Ws limit and three-minute interval must be respected.
Q02What information is needed to quote 6SL3000-0KH14-0AA0?
Provide the Basic Line Module MLFB, supply voltage, frame size, resistor arrangement, cabinet photographs and failed-part label.
Q03Why must cooling clearance be reviewed for 6SL3000-0KH14-0AA0?
The resistor becomes hot during precharge; inadequate ventilation or contact with heat-sensitive material can damage the cabinet and wiring.
Q04Can a resistor with the same nominal ohms replace 6SL3000-0KH14-0AA0?
Not by resistance alone. Pulse energy, voltage, insulation, mounting, temperature and Siemens system approval must also match.
Q05What should be tested after replacing 6SL3000-0KH14-0AA0?
Verify resistance, insulation, wiring, contactor sequence, precharge time, DC-link rise, temperature clearance and normal line-module diagnostics.
Recommended Models
| MSF-045 525 2 C-N-AAU | 6308 D40/D90X23 | ABB DO561 1TNE968902R2201 |
| Wago 750-301 | STEP-PS/1AC/12DC/5 2868583 | 1125WBN-10PKG |
| ABB 2CDG110042R0011 | 53.602.0E AC5360B.0Z | X20AO2622 |
| LK3023 | AP-101-11-2 | 1F83-71 2 |
| X20BM26 | MTN647593 | 140ACO13000 |
| WMG 4371944-125 | Danfoss MCD5-0428C-T5-G4X-00-CV2 175G5540 | 5T0001D000700F-000 |
| MPN 44-H 4.3-B 25.20-DK1TR | DLC-MASTER | MCE3 |
| 3IF050.6 | Siemens 1PH8165-1DF03-0CC1 | 6ES7422-1HH00-0AA0 |
| ABB 1SAZ211201R1031 | DRE90M4BE2 | AI354 |
| DDTC001 | 11-PKZ | EAMK-A-D32-44A/C |