Home>PLC>Siemens 6SL3210-1KE15-8UB2 SINAMICS G120C Converter

Hot Categories

Siemens 6SL3210-1KE15-8UB2 SINAMICS G120C Converter

Siemens 6SL3210-1KE15-8UB2 SINAMICS G120C Converter

Item NO.: 3760227

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameSiemens 6SL3210-1KE15-8UB2 SINAMICS G120C Converter
  • Item NO.3760227
  • Weight1.0000 kg = 2.2046 lb = 35.2740 oz
  • CategoryPLC
  • BrandSiemens
  • Creation Time2026-09-04
SINAMICS G120C | Compact drive with USS and Modbus RTU

Siemens 6SL3210-1KE15-8UB2 SINAMICS G120C Converter

A compact three-phase converter with integrated control I/O, Safe Torque Off and an unfiltered 380–480 V power section.

BrandSiemens
Model6SL3210-1KE15-8UB2
Product TypeSINAMICS G120C Compact Converter
01

Product Profile

6SL3210-1KE15-8UB2 is a SINAMICS G120C compact converter for variable-speed motor control. It combines the power stage, control functions, field I/O and serial communication in one frame-size AA device.

This exact UB2 variant is unfiltered, uses an external 24 V control supply and communicates through USS or Modbus RTU. It should not be confused with PROFINET, PROFIBUS or filtered G120C order variants.

02

Technical Data

Manufacturer Siemens
Article Number 6SL3210-1KE15-8UB2
Product Family SINAMICS G120C
Product Type Compact frequency converter
Line Supply 380 to 480 V AC, 3 phase; +10% / -20%
Line Frequency 47 to 63 Hz
Low-Overload Power 2.2 kW
High-Overload Power 1.5 kW
Output Current, Low / High Overload 5.60 / 4.10 A
Rated / Maximum Output Current 5.80 / 8.20 A
Input Current, Low / High Overload 7.40 / 6.00 A
Pulse Frequency 4 kHz
Output Frequency 0 to 240 Hz vector; 0 to 550 Hz V/f
Control Methods Linear, square-law and parameterized V/f; FCC; ECO; sensorless vector
Communication USS and Modbus RTU
Digital Inputs 6
Digital Outputs 2: one relay and one transistor
Analog Interface 1 differential analog/digital input and 1 analog output
Motor Temperature Input PTC, KTY or Thermo-Click
Safety Function Integrated Safe Torque Off
EMC Filter Unfiltered
Control Supply External 24 V DC
Degree of Protection IP20 / UL open type
Frame Size FSAA
Cooling Integrated air cooling
Operating Ambient -10 to 40 °C at rated conditions
Lifecycle Status Active
03

System Role

  • Controls induction-motor speed and torque using V/f or sensorless vector algorithms selected for the machine duty.
  • Integrates basic field signals directly through the onboard digital, analog and temperature-monitoring interfaces.
  • Provides Safe Torque Off as an embedded safety function for an appropriately engineered machine circuit.
  • Connects to a serial automation network through the supported USS or Modbus RTU interface.
  • Uses its internal fan to manage converter losses within the documented cabinet environment.
04

Compatibility

  • Match the three-phase supply voltage, motor current and overload duty to the exact application before parameterization.
  • Provide the required external 24 V control supply for this UB2 order variant.
  • Do not specify this article when an integrated EMC filter or a different fieldbus interface is mandatory.
  • Coordinate Safe Torque Off wiring with the machine risk assessment and the complete safety circuit.
  • Check cabinet clearance, airflow, grounding and motor-cable requirements for the FSAA installation.
05

Applications

  • Compact conveyors, pumps and fans requiring variable-speed control from a three-phase industrial supply.
  • Standalone machines using Modbus RTU or USS for basic supervisory communication.
  • OEM panels that can use onboard I/O without a separate drive-interface module.
  • Motor installations that require integrated Safe Torque Off within the validated safety design.
06

FAQ

What power ratings apply to this exact converter?

It is rated 2.2 kW for low-overload duty and 1.5 kW for high-overload duty.

Which communication protocols are integrated?

The UB2 version supports USS and Modbus RTU.

Does this article include an EMC filter?

No. The official product configuration identifies it as unfiltered.

Is a separate control supply required?

Yes. This version uses an external 24 V DC control supply.

Which safety function is integrated?

Safe Torque Off is integrated, but its use still requires a complete engineered safety circuit.

What must be checked before replacing a similar G120C?

Verify the full order code, supply, overload duty, fieldbus, filter, external 24 V supply and frame dimensions.

IndustryParts | Industrial automation product enquiries and spare-parts support

You May Also Like