Siemens 6SL3210-1PE18-0AL1 SINAMICS PM240-2 Power Module
A frame-size FSA PM240-2 power module with integrated braking chopper for compatible SINAMICS G120 control units.
Key Information
6SL3210-1PE18-0AL1 is a SINAMICS PM240-2 modular power stage for three-phase 380 to 480 V supply systems. The article combines a Class A input filter and an integrated braking chopper in the compact FSA enclosure.
The module is rated for 3 kW low-overload duty or 2.2 kW high-overload duty. It forms a complete converter only after a compatible SINAMICS control unit is installed and configured for the motor and machine.
Functions
- Converts the incoming three-phase AC supply into controlled motor power under commands from the fitted control unit.
- Provides an internal braking chopper for applications that route regenerative energy to a correctly selected external braking resistor.
- Supports low-overload and high-overload operating profiles so selection can follow the torque and acceleration demands of the load.
- Uses forced internal air cooling to remove power-stage heat from the FSA enclosure.
- Integrates the Class A filter required by the stated article configuration.
Specifications
| Manufacturer | Siemens |
|---|---|
| Article Number | 6SL3210-1PE18-0AL1 |
| Product Family | SINAMICS G120 PM240-2 |
| Input Supply | 3 AC 380–480 V, +10 / -10%, 47–63 Hz |
| Low-Overload Rating | 3 kW at -10 to +40 °C |
| High-Overload Rating | 2.2 kW at -10 to +50 °C |
| Overload Profile | 200% for 3 s / 150% for 57 s / 100% for 240 s |
| Input Filter | Integrated Class A filter |
| Braking Chopper | Integrated |
| Frame Size | FSA |
| Dimensions | 196 × 73 × 165 mm (H × W × D) |
| Protection | IP20 without control unit or operator panel |
| Control-Unit Requirement | Compatible control unit, firmware V4.6 or later |
| Cooling Airflow | 0.005 m³/s |
| Installation Altitude | Up to 1,000 m without derating |
| Efficiency Class | IE2 |
| Lifecycle | Active product |
Installation
- Mount the FSA unit vertically with the specified cooling clearances and keep the internal airflow path unobstructed.
- Verify line voltage, protective conductor, motor cable, braking-resistor duty and electromagnetic-compatibility measures before energizing.
- Fit a released SINAMICS control unit and retain the required firmware level before loading motor and application parameters.
- Use the PM240-2 installation procedure for power-terminal torque, shielding, grounding and cabinet ventilation.
- Commission the motor only after the rating plate data and the intended low- or high-overload duty have been confirmed.
Lifecycle
- Siemens classifies this article as an active product.
- The complete 6SL3210-1PE18-0AL1 order number identifies the filtered power-stage variant and must be retained in procurement records.
- Replacement planning should include the installed control unit, its firmware, the parameter backup and the external braking arrangement.
- Before exchanging a module, record the motor rating, supply conditions and cabinet cooling design rather than selecting on kilowatt rating alone.