Siemens 6SL3210-1PE22-7UL0 is an unfiltered SINAMICS PM240-2 Power Module with an integrated braking chopper. Designed for three-phase 380-480 V AC systems, the FSC module is rated 7.5 kW for high-overload duty and 11 kW for low-overload duty and is supplied without a Control Unit or operator panel.
02Engineering Data
| Manufacturer | Siemens |
|---|---|
| Article Number | 6SL3210-1PE22-7UL0 |
| Product Family | SINAMICS PM240-2 |
| Input Supply | Three-phase 380-480 V AC, +/-10%, 47-63 Hz |
| High-Overload Power | 7.5 kW |
| High-Overload Duty | 200% for 3 s, 150% for 57 s, 100% for 240 s |
| Low-Overload Power | 11 kW |
| Low-Overload Duty | 150% for 3 s, 110% for 57 s, 100% for 240 s |
| EMC Filter | Without integrated filter |
| Braking Chopper | Integrated |
| Frame Size | FSC |
| Operating Temperature | -10 to +50 degrees C high overload; -10 to +40 degrees C low overload |
| Cooling | Internal air cooling |
| Degree of Protection | IP20 |
| Control Unit | Not included |
| Operator Panel | Not included |
| Control-Unit Firmware Release | V4.6 or later |
03Functions
Operational Functions
- Provides the power stage for a modular SINAMICS G120 drive.
- Integrated braking chopper supports the correctly engineered braking resistor.
- High-overload and low-overload ratings allow selection by the actual load profile.
- The unfiltered construction permits an external EMC solution tailored to the installation.
- FSC mechanics use internal air cooling and require the specified cabinet airflow.
- Drive control, communication and I/O are determined by the selected compatible Control Unit.
Product Identity
- Manufacturer: Siemens
- Model: 6SL3210-1PE22-7UL0
- Product Type: SINAMICS PM240-2 Unfiltered Power Module
04System Integration
- Choose a Siemens-approved Control Unit with the required firmware, communication and safety functions.
- Engineer the external EMC filter or line-side components for the installation category and cable length.
- Match motor voltage, current, power, overload duty, switching frequency and thermal requirements.
- Select mains protection, braking resistor, grounding, cabling and cabinet cooling according to the current manual.
- A filtered PM240-2 suffix or a different frame size is not a direct substitute without redesign.
05Applications
Typical Uses
- Medium-power pumps, fans, conveyors and machine axes.
- Applications requiring 7.5 kW high-overload or 11 kW low-overload duty.
- Systems using an external EMC solution and the built-in braking chopper.
- Maintenance replacement in modular SINAMICS G120 drive assemblies.
Selection Boundary
- Select the overload class from the real motor and load duty.
- Engineer the external filter and braking resistor when required.
- Match the Control Unit, firmware, frame, protection and cooling.
06Lifecycle
- Confirm the current Siemens lifecycle and availability for the exact suffix before procurement.
- Back up the Control Unit parameters and record the fitted Power Module, motor, braking and line-side configuration.
- Document overload class, switching frequency, EMC solution, protective devices, cables, grounding and cooling.
- Do not substitute another PM240-2 by power rating alone; filter, frame, current, firmware release and regional configuration must match.
- After replacement, verify DC-link voltage, motor current, direction, braking, alarms, EMC, overload performance and temperature.
FAQFrequently Asked Questions
What is Siemens 6SL3210-1PE22-7UL0?
It is an unfiltered SINAMICS PM240-2 Power Module with an integrated braking chopper.
What power ratings apply?
Siemens lists 7.5 kW for high-overload duty and 11 kW for low-overload duty.
Does it have an integrated EMC filter?
No. The official description identifies this suffix as without filter, so the required external EMC design must be engineered.
Are a Control Unit and operator panel included?
No. The product is supplied without both components.
Which Control Unit firmware release is required?
The product record states release for Control Unit firmware V4.6 or later.
What should be checked after installation?
Verify DC-link behavior, motor current, direction, braking, communications, alarms, external EMC measures, overload duty and cooling.
+Recommended Models
| LR9502 | EL6692 | IC200UDR005-BD、IC200UEX011-B |
| 1756-0b16e/A | KXA-GPI-GEN-R 0798-9700-302 | LA-21-L1L2-N |
| JL325-61001 | MSR138.1DP 440R-M23084 | ABB DO571 A0 -1TNE968902R2202 |
| M/P960.1 DC30V | 990023-0064 | 9002/11-199-030-00 |
| TIS-DMX-48 | STD150 | 4269-462.04 |
| 994-14D | ACU-485CNV-U | V61R513A-A2000 |
| 125-065-769 | 110EET | E520 |
| 950-0487 MSU-3 R90550 MSU3 | VC7936ZZ11/U VC7936-11 | BMXXBE1000 |
| 1746-OB32 | CCT15369 | ABB CP-E24/5.0 1SVR427034R0000 |
| CNV-W-3 | PXC64-U | 414AR-BJ-000-000 |