Siemens 6SL3210-1PE31-5UL0 SINAMICS G120 PM240-2 Power Module
A 75 kW low-overload / 55 kW high-overload PM240-2 module for 380–480 V systems requiring a separately engineered EMC arrangement.
Overview
6SL3210-1PE31-5UL0 is the unfiltered FSF version of the SINAMICS G120 PM240-2 power module. It is intended for installations where filtering and EMC compliance are managed at the cabinet or machine level.
The power stage supplies up to 145 A rated output in low-overload duty and 110 A in high-overload duty. An integrated braking chopper is available for connection to a suitable external braking resistor.
Specifications
| Manufacturer | Siemens |
|---|---|
| Article Number | 6SL3210-1PE31-5UL0 |
| Product Family | SINAMICS G120 / PM240-2 |
| Input Supply | 3 AC 380–480 V, ±10%, 47–63 Hz |
| Rated Power, Low Overload | 75 kW |
| Rated Power, High Overload | 55 kW |
| Input Current | 140 A LO / 117 A HO |
| Output Current | 145 A LO / 110 A HO |
| Maximum Output Current | 220 A |
| Pulse Frequency | 2 kHz |
| Output Frequency | 0–200 Hz vector / 0–550 Hz V/f |
| EMC Filter | Not integrated |
| Power Factor | 0.95 |
| Efficiency | 0.98 |
| Power Loss | 1.78 kW |
| Sound Pressure | 68 dB |
| Cooling Air Requirement | 0.153 m³/s, internal air cooling |
| Motor Cable Limit | 300 m shielded / 450 m unshielded |
| Protection | IP20 / UL open type |
Features
- The UL0 suffix identifies an unfiltered power module and should be retained exactly in procurement and maintenance records.
- Published low- and high-overload current values provide separate sizing points for variable-torque and heavier cyclic duties.
- The internal air-cooling path is sized for the FSF power stage and depends on correct cabinet clearances.
- A braking chopper is incorporated, while the resistor and its thermal protection remain external engineering items.
- Vector and V/f output-frequency ranges support a broad selection of industrial motor-control tasks.
Applications
- Drive cabinets using centralized line filtering or another documented EMC solution.
- 75 kW low-overload fan and pump duties in modular SINAMICS G120 architectures.
- 55 kW high-overload material-handling and process-machine applications.
- Retrofit projects that must match an existing FSF unfiltered PM240-2 footprint and cooling plan.
Lifecycle
- Identify the spare as 6SL3210-1PE31-5UL0 rather than substituting the heavier filtered AL0 variant without engineering review.
- Compare line supply, motor current, overload cycle, pulse frequency and external filter arrangement.
- Inspect fans, airflow path and cabinet heat removal as part of scheduled drive maintenance.
- Back up parameters and document the Control Unit, option modules and braking resistor before replacement.
FAQ
Does 6SL3210-1PE31-5UL0 contain an EMC filter?
No. 6SL3210-1PE31-5UL0 is the unfiltered FSF article.
What output current is published for 6SL3210-1PE31-5UL0?
The ratings are 145 A low overload, 110 A high overload and 220 A maximum output current.
Is 6SL3210-1PE31-5UL0 the same as the AL0 version?
No. The UL0 model is unfiltered; the AL0 article integrates a Class A filter.
What cooling airflow does 6SL3210-1PE31-5UL0 require?
The official data specifies 0.153 m³/s of internal cooling airflow.
Can 6SL3210-1PE31-5UL0 use long motor cables?
The documented limits are 300 m shielded and 450 m unshielded, subject to the complete installation design.
What should accompany a 6SL3210-1PE31-5UL0 enquiry?
Provide motor data, load duty, supply, Control Unit, EMC solution, cable length, braking details and cabinet conditions.
Recommended Models
| IZMX-SR230AD-1 | 750-342 | PFD-402-N1 |
| SMC-3 150-C9NB | 4098-5260 | MS-FEC-1610-0 |
| VAA-4E4A-G11-ZAJ/EA2L-F 220205 | GX1230 | MNX 45-80 CS94202 |
| GDP-CBL-OBD/ETH-02 | 683832 | SEL-9321 932160X |
| 616102R5Z31002M | WV-S2110 | LT8155A |
| 6EV5002-0BC | 5WG1527-1AB02 | M71C-2000-595-TN |
| AJ65BTB2-16D | TY-FB9FDD | RH 53A |
| LJ-G5001 | P8 R 8 DIN - 8 | 751322 220-000437-403 |
| M1032-61602 B-M1032-94302-1 | DM3110 | EPX-410D |
| U20NRUD300 000 RS485 | DC-9204 | DPS-750XB E98791-010 |