Home>PLC>Siemens 6SL3210-1PE32-5UL0 SINAMICS G120 PM240-2 Power Module

Hot Categories

Siemens 6SL3210-1PE32-5UL0 SINAMICS G120 PM240-2 Power Module

Siemens 6SL3210-1PE32-5UL0 SINAMICS G120 PM240-2 Power Module

Item NO.: 3762838

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameSiemens 6SL3210-1PE32-5UL0 SINAMICS G120 PM240-2 Power Module
  • Item NO.3762838
  • Weight61.0000 kg = 134.4820 lb = 2151.7117 oz
  • CategoryPLC
  • BrandSiemens
  • Creation Time2026-09-07
SINAMICS G120 | 132 kW unfiltered FSF power stage

Siemens 6SL3210-1PE32-5UL0 SINAMICS G120 PM240-2 Power Module

An unfiltered 380–480 V PM240-2 rated at 132 kW low overload and 110 kW high overload.

BrandSiemens
Model6SL3210-1PE32-5UL0
Product TypeUnfiltered PM240-2 Power Module
01

Product Overview

6SL3210-1PE32-5UL0 is the unfiltered FSF version of the SINAMICS G120 PM240-2 power module. It provides a 132 kW low-overload or 110 kW high-overload power stage for modular drive systems.

The module includes a braking chopper but does not contain an EMC filter. The system designer therefore selects the required external filtering and installation measures for the machine or plant.

02

Performance

  • Rated output current is 250 A for low overload and 205 A for high overload.
  • Maximum output current is 410 A within the documented overload behavior.
  • Vector-control output frequency extends to 200 Hz and V/f control extends to 550 Hz.
  • Power factor is 0.95 and efficiency is 0.98 under the stated technical conditions.
  • Internal cooling requires 0.153 m³/s of airflow through the FSF module.
03

Technical Details

Manufacturer Siemens
Article Number 6SL3210-1PE32-5UL0
Product Family SINAMICS G120 / PM240-2
Input Supply 3 AC 380–480 V, ±10%, 47–63 Hz
Rated Power, LO 132 kW
Rated Power, HO 110 kW
Rated Input Current 242 A LO / 218 A HO
Rated Output Current 250 A LO / 205 A HO
Maximum Output Current 410 A
Output Frequency 0–200 Hz vector / 0–550 Hz V/f
EMC Filter Not integrated
Cooling Internal air cooling, 0.153 m³/s
Motor Cable Limit 300 m shielded / 450 m unshielded
Protection / Frame IP20 / UL open type; FSF
04

System Integration

  • Provide the external EMC arrangement required for the target installation category.
  • Use a compatible SINAMICS Control Unit for communication, I/O, control and any required safety functions.
  • Size line protection, motor conductors and braking resistor against the selected overload profile.
  • Maintain the FSF airflow path and account for drive losses in cabinet thermal calculations.
  • Verify motor-cable length and shielding against the complete drive-system design.
05

Applications

  • Large variable-torque pumps and fans using 132 kW low-overload duty.
  • Material-handling and process machinery requiring the 110 kW high-overload rating.
  • Control cabinets with a centrally engineered EMC filter arrangement.
  • SINAMICS G120 systems needing a replaceable unfiltered FSF power stage.
06

FAQ

Is 6SL3210-1PE32-5UL0 filtered?

No. 6SL3210-1PE32-5UL0 is the unfiltered UL0 variant.

What power ratings apply to 6SL3210-1PE32-5UL0?

It is rated 132 kW for low overload and 110 kW for high overload.

What is the output current of 6SL3210-1PE32-5UL0?

The ratings are 250 A low overload, 205 A high overload and 410 A maximum output current.

Does 6SL3210-1PE32-5UL0 include a braking chopper?

Yes. The braking chopper is built in, while the braking resistor remains an external selection.

How does 6SL3210-1PE32-5UL0 differ from 6SL3210-1PE32-5AL0?

The UL0 unit has no integrated filter; the otherwise related AL0 version includes a Class A filter and has a higher technical net weight.

What should be specified with a 6SL3210-1PE32-5UL0 enquiry?

Provide the motor, duty cycle, Control Unit, supply, EMC plan, cable length, braking load and cabinet cooling data.

You May Also Like