Siemens 6SL3210-1PE34-8CL0 SINAMICS G120/S120 PM240-2 Power Module
An FSG power module with integrated Class C3 filtering and braking chopper for 250/200 kW drive duty.
Technical Summary
6SL3210-1PE34-8CL0 is a frame-size FSG SINAMICS G120/S120 PM240-2 Power Module with an integrated Class C3 EMC filter and braking chopper. It operates from a three-phase 380 to 480 V supply.
The module is rated for 250 kW low-overload duty and 200 kW high-overload duty. The Control Unit and operator panel are separate components in the modular drive architecture.
Specifications
| Manufacturer | Siemens |
|---|---|
| Article Number | 6SL3210-1PE34-8CL0 |
| Product Family | SINAMICS G120/S120 / PM240-2 |
| Input Supply | 3 AC 380–480 V, ±10%, 47–63 Hz |
| Rated Power, Low Overload | 250 kW |
| Rated Power, High Overload | 200 kW |
| Rated Input Current | 470 A LO / 400 A HO |
| Rated Output Current | 477 A LO / 370 A HO |
| S6 Current, 40% Duty | 572 A |
| Maximum Output Current | 740 A |
| Pulse Frequency | 2 kHz rated; 8 kHz maximum |
| Integrated EMC Filter | Class C3 |
| Power Factor / Efficiency | 0.90 / 0.98 |
| Power Loss | 6.18 kW |
| Cooling | Internal air cooling, 0.210 m³/s |
| Operating Temperature | -20 to +40 °C LO / -20 to +50 °C HO |
| Protection / Frame | IP20 / UL open type; FSG |
Features
- Integrated Class C3 filtering defines the EMC variant of 6SL3210-1PE34-8CL0.
- An integrated braking chopper supports a correctly engineered external braking resistor.
- The 740 A peak output supports the documented short-duration overload profile.
- Internal forced-air cooling removes heat from the 250 kW FSG power stage.
- Separate low- and high-overload ratings support different machine torque cycles.
Compatibility
- Pair the power module with a supported SINAMICS Control Unit and released firmware.
- Keep the Class C3 EMC selection consistent with the cabinet, cable and installation category.
- Select line protection, conductors, motor cable and braking resistor from the FSG current and overload data.
- Provide lifting and service access suitable for the 1000 × 305 × 357 mm module.
- Verify the Control Unit, panel and option modules separately because they are not included with the power stage.
Replacement
- Use the full 6SL3210-1PE34-8CL0 identifier so the Class C3 filter variant is not confused with the adjacent suffix.
- Confirm whether the machine uses the 250 kW low-overload or 200 kW high-overload profile.
- Back up parameters and record the Control Unit firmware, motor data and braking circuit before exchange.
- Verify cabinet airflow, mounting dimensions, lifting provisions and cable terminations.
- Recommission the motor data and functional checks before returning the drive to production.
FAQ
What power ratings apply to 6SL3210-1PE34-8CL0?
6SL3210-1PE34-8CL0 is rated 250 kW for low overload and 200 kW for high overload.
Which EMC filter is integrated in 6SL3210-1PE34-8CL0?
6SL3210-1PE34-8CL0 includes a Class C3 filter.
What maximum output current can 6SL3210-1PE34-8CL0 provide?
The documented maximum output current is 740 A.
Does 6SL3210-1PE34-8CL0 include a braking chopper?
Yes. The braking chopper is integrated; the external resistor remains an engineered system component.
Which frame size is used by 6SL3210-1PE34-8CL0?
6SL3210-1PE34-8CL0 uses frame size FSG and measures 1000 × 305 × 357 mm.
What must be checked before replacing 6SL3210-1PE34-8CL0?
Confirm filter class, overload duty, Control Unit, firmware, motor current, braking circuit, airflow, weight and mechanical access.
Recommended Models
| D-1101-RSG2100 RJ45TX01 | C-Bus2 5034-NIRT | RS-481 |
| I/P DMX | TE-6300W-110 | U20NRUD300 000 / RS485 |
| ABB 30.640.5 | ITEM3-2000U016000 | MN-S3 |
| PREMTB001 | 203LS-D | FX2NC-32MT-DSS |
| BZMD1-A63 | 813S-V3-400V | R7847 C1005 97-4685E |
| 1C31203G01 | iQEC035-1201U50004 | ABB 2CDG 110 065 R0011 |
| 19-HD ACTFM1UF2SC3PMM | SF61B | MX-OPT-F2.0-L43-L51 |
| FERMAX 2425 | MPW-6 RS-232 PN:096151 | 1D75 |
| MTL7728 | 3HE05833CAAA01 | 15784 3V-2Z |
| AV3105 | ABB RXMB 1 1MRK 000 863-AN | BC-GT30 0103-003-00 |