Home>DCS>Woodward 8440-2080 easYgen-2300-5/P1 Genset Controller

Hot Categories

Woodward 8440-2080 easYgen-2300-5/P1 Genset Controller

Woodward 8440-2080 easYgen-2300-5/P1 Genset Controller

Item NO.: 3808961

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameWoodward 8440-2080 easYgen-2300-5/P1 Genset Controller
  • Item NO.3808961
  • Weight1.0000 kg = 2.2046 lb = 35.2740 oz
  • CategoryDCS
  • BrandWoodward
  • Creation Time2026-10-25
INDUSTRIAL PART RECORDeasYgen-2000
EASYGEN-2300-5/P1 · 5 A CT INPUTS · SIMPLE PARALLELING

Woodward 8440-2080 easYgen-2300-5/P1 Genset Controller

A front-panel genset controller for easYgen-2000 simple-paralleling applications with 5 A current-transformer inputs.

Model2300-5/P1
CT input5 A
Parallel unitsUp to 16
PRODUCT DOSSIER

Product Profile

01

Woodward 8440-2080 is the easYgen-2300-5/P1 genset controller in the easYgen-2000 simple-paralleling line.

The controller supports single-unit mains paralleling and multiple-unit island paralleling for up to 16 generating sets. It combines generator and mains measurement, breaker synchronization, protection logic and front-panel operation.

This execution uses 5 A current-transformer inputs and the P1 communication and I/O configuration identified in Woodward product literature.

PUBLISHED EVIDENCE

Technical Data

02
Manufacturer

Woodward

Exact part number

8440-2080

Product model

easYgen-2300-5/P1

Product line

easYgen-2000 simple paralleling

Mounting

Front-panel controller with display

Current-transformer input

5 A

Operating modes

Automatic, Manual and Stop

Paralleling capability

Single unit with mains; island load sharing up to 16 gensets

Discrete inputs

8 configurable

Discrete outputs

6 configurable

Analog inputs

3 configurable

Analog outputs

2 configurable

CAN interfaces

1

Serial interface

RS-485 Modbus RTU slave

Event recorder

300 entries with real-time clock

CONTROLLED PATH

System Role

03
1

Export the controller file

Save the parameter set, LogicsManager configuration, event history and communication settings.

2

Document measurement circuits

Record CT ratio, voltage inputs, breaker feedback, engine interface and terminal wiring.

3

Commission in controlled stages

Prove measurements, protections, breaker logic, synchronization, load sharing and emergency response.

MATCH CRITERIA

Compatibility

04

Integrated synchronization

The controller manages generator and mains breaker synchronization for approved operating modes.

Load and var sharing

Multiple generating sets can share load in island operation within the documented architecture.

Configurable protection

Generator, engine and mains protection functions are combined with programmable control logic.

Local operating interface

The front display, soft keys and event recorder support operation and maintenance review.

FIELD DUTY

Applications

05

Single-generator mains paralleling

Synchronizing a generating set to the utility and controlling the documented breaker sequence.

Multi-genset island operation

Sharing load among up to 16 units with coordinated start and stop logic.

Standby generation

Managing automatic mains-failure response, generator protection and return transfer.

GLOBAL INDUSTRIAL PARTS SUPPORT

About IndustryParts

https://www.industryparts.com/

Exact-model records keep 8440-2080 traceable

IndustryParts keeps the requested identity, quantity, label evidence and delivery record together so the proposed supply can be checked against the installed application before dispatch.

Label evidence retained
System context reviewed
Dispatch record controlled
IndustryParts industrial automation support
PROCUREMENT QUESTIONS

FAQ

06
Q01

What exact easYgen execution is 8440-2080?

Woodward lists 8440-2080 as easYgen-2300-5/P1 with 5 A current-transformer inputs.

Q02

How many generating sets can 8440-2080 share load with in island operation?

Woodward documentation states multiple-unit island paralleling for up to 16 gensets.

Q03

Which configuration records belong with 8440-2080?

Retain the full parameter file, LogicsManager logic, CT and VT ratios, breaker sequence, event log and communication settings.

Q04

What service cable is required for 8440-2080 configuration?

Woodward identifies its proprietary DPC service connection for controller configuration.

Q05

What proves 8440-2080 is ready after replacement?

Verify measurements, protections, breaker feedback, synchronization, load and var sharing, communications and the approved emergency sequence.

You May Also Like