FA-M3ENGINEERING RECORD
16 RELAY CONTACTS · 8 POINTS PER COMMON · 2 A PER POINT

Yokogawa F3YC16-0N 16-Point Relay Output Module

A 16-point relay-contact output module for FA-M3 systems, with two eight-point common groups.

01
PRODUCT CONTEXT

Product Overview

F3YC16-0N is the Yokogawa FA-M3 relay output module with sixteen mechanically isolated contact outputs arranged as two groups of eight points per common.

The module switches documented DC or AC loads and provides LED output indication. It contains neither an output fuse nor a surge-protection circuit, so branch protection and inductive-load suppression belong in the external design.

Yokogawa warns against mixing DC and AC loads on one module or using different AC sources on separate groups. Wiring must follow one approved supply strategy for the complete module.

02
OPERATING VALUE

Performance

Relay isolation

Uses mechanical relay contacts to separate field switching from the controller logic.

Dual common groups

Organizes sixteen outputs as two eight-point groups for controlled distribution.

Load switching

Supports documented resistive AC or DC loads within the point and common limits.

Visual status

Provides front-panel LED indication for the output states.

03
CONTROLLED DATA

Technical Details

Manufacturer Yokogawa Exact model F3YC16-0N
Product designation Relay Output Module Output points 16
Points per common 8 Isolation Mechanical relay contact
Rated DC range 5 to 24 V DC; 125 V DC maximum Rated AC range 100 to 240 V AC; 264 V AC maximum
Maximum current 2 A per point; 8 A per common, resistive Minimum load 5 V DC, 10 mA
Response time 10 ms maximum ON or OFF Mechanical life 20 million operations or more
Electrical life 100,000 operations at rated load Internal protection No surge protector; no fuse
Internal current 380 mA at 5 V DC External connection 18-point M3.5 terminal block

About IndustryParts

https://www.industryparts.com/

Relay loading is reviewed point by point

IndustryParts keeps the exact module, load schedule, common grouping and protection plan together before supply.

  • Exact submitted model retained
  • Installed-system evidence reviewed
  • Quotation identity kept traceable
IndustryParts team supporting industrial component verification
04
FIELD SEQUENCE

System Integration

01

Separate the supply strategy

Do not mix DC and AC loads on the same module or use different AC sources across groups.

02

Protect external circuits

Provide approved branch protection and suppression for inductive loads because the module has no internal fuse or surge protector.

03

Prove each output

Test polarity or phase, contact operation, load current and the safe state for all sixteen channels.

05
APPLICATION FIT

Applications

01

Machine interlocks

Switching approved contactor, solenoid or indication loads in an FA-M3 control panel.

02

Mixed process equipment

Providing isolated relay contacts where transistor output characteristics are unsuitable.

03

Controlled module exchange

Replacing a relay module while preserving the load and common-group schedule.

06
CUSTOMER QUESTIONS

FAQ

QUESTION 01

Can DC and AC loads be mixed on F3YC16-0N?

No. Yokogawa instructs users not to mix DC and AC loads on one module.

QUESTION 02

Does F3YC16-0N include output fuses or surge suppression?

No. External branch protection and appropriate suppression for inductive loads must be provided.

QUESTION 03

What load schedule should accompany a F3YC16-0N enquiry?

Provide voltage type, steady and inrush current, switching frequency, common grouping and suppression for every point.

QUESTION 04

Can two different AC sources be used across the two common groups of F3YC16-0N?

No. Yokogawa warns against different AC sources on separate groups of the module.

QUESTION 05

What proves F3YC16-0N is ready after installation?

Verify all sixteen contacts, common-group wiring, load current, external protection, safe states and the complete output schedule.

07
SELECTION SUPPORT

Recommended Models

ENQUIRY INFORMATION

Send the complete F3YC16-0N identity

Include requested quantity, destination and the installed-system evidence needed for compatibility review.