ABB CM598-CN CANopen Master Communication Module
A dedicated CANopen master for organizing cyclic process exchange, parameter services and network supervision from an ABB AC500 controller.
Key Information
CM598-CN adds a CANopen master interface to a supported AC500 processor installation. It combines a netX communication processor, dual-port exchange memory and a front CAN connector to manage a field network of slave devices. Receive and transmit process-data resources are sized independently for deterministic application mapping.
Functions
- Controls CANopen network management from the master side of the bus.
- Exchanges cyclic process values through configured receive and transmit PDOs.
- Uses SDO client services for parameter-oriented communication with slave nodes.
- Supports heartbeat and node-guarding mechanisms for device supervision.
- Reports module and CAN network state through dedicated front indicators.
Specifications
| Manufacturer | ABB |
|---|---|
| Article Number | 1SAP173800R0001 |
| Product Family | AC500 |
| Network Role | CANopen master |
| Supported CAN Frames | CAN 2A and CAN 2B |
| Transfer Rate | 10 kbit/s to 1 Mbit/s |
| Connector | Pluggable COMBICON, 2 x 5-pin |
| Communication Processor | Hilscher netX 100 |
| Communication Interface | 16 kB dual-port RAM |
| Maximum Slave Nodes | 126 |
| Receive PDO Capacity | Maximum 512 |
| Transmit PDO Capacity | Maximum 512 |
| Process Data Capacity | Maximum 3584 bytes each for input and output |
| Typical Current Consumption | 65 mA |
| Product Lifecycle | Active |
Installation
- Mount the standard module on a compatible TB5xx terminal base and keep the XC article separate for extreme environments.
- Set a unique network-node plan and choose one CAN transfer rate for every device on the segment.
- Apply correct bus topology and termination at the two physical ends of the CAN line.
- Import and review device descriptions before mapping PDOs or issuing SDO parameters.
- Commission slave nodes in stages and use the CAN-RUN and CAN-ERR indications during diagnosis.
Lifecycle
- ABB identifies the standard CM598-CN article as Active.
- Store the CANopen project, node identifiers, PDO map and parameter records with the controller backup.
- Review controller and communication-module firmware when expanding an established network.
- Keep spare connectors and termination information with the maintenance documentation.
- Validate node supervision and all mapped process values after a module exchange.