ABB DO562 16-Channel Digital Output Module
A sixteen-channel 24 V DC transistor output module with one isolated group, 0.5 A channel rating and two removable terminal blocks.
Product Overview
ABB DO562, article 1SAP230900R0000, provides sixteen 24 V DC transistor outputs in one isolated group. The module maps two bytes of output process data and uses separate 9-pin and 11-pin terminal blocks for the field channels.
Performance
- Sixteen non-latching transistor outputs provide 0.5 A per channel at 24 V DC.
- The single output group supports a maximum total current of 8 A.
- Maximum switching delays are 50 µs for turn-on and 200 µs for turn-off.
- One yellow LED indicates the state of every output.
- Maximum internal power dissipation is 1.4 W.
Technical Details
| Manufacturer | ABB |
|---|---|
| Article Number | 1SAP230900R0000 |
| Product Family | AC500 S500-eCo |
| Output Count | 16 transistor outputs |
| Output Grouping | 1 group of 16 channels |
| Nominal Output Voltage | 24 V DC |
| Rated Current per Channel | 0.5 A |
| Maximum Current per Group | 8 A |
| Output Data Length | 2 bytes |
| Maximum Output-On Delay | 50 µs |
| Maximum Output-Off Delay | 200 µs |
| Maximum Lamp Load | 5 W |
| Output Protection | External 3 A fast fuse per channel |
| Short-Circuit / Overload Protection | Not integrated |
| Terminal Blocks | One 9-pin and one 11-pin block, ordered separately |
| Maximum Module Dissipation | 1.4 W |
| Lifecycle | Active |
System Integration
- Install one compatible 9-pin and one compatible 11-pin S500-eCo terminal block.
- Connect the common 24 V process supply to UP terminal 19 and ZP terminal 20.
- Provide external channel fusing and inductive-load suppression because protection is not integrated.
- Maintain natural convection and apply the documented group-load derating for vertical mounting.
- Hot swap is not supported for DO562; de-energize the field circuit before service.
Applications
- Compact machines requiring sixteen 24 V DC actuator outputs.
- Valve, relay and indicator control within the documented channel and group limits.
- Central or supported remote S500-eCo I/O expansion.
- Panel designs benefiting from removable screw or spring terminal blocks.
- Active maintenance spares for article 1SAP230900R0000.
FAQ
How many outputs does ABB DO562 provide?
It provides sixteen 24 V DC transistor outputs.
What is the current limit for the full output group?
ABB specifies 0.5 A per channel and a maximum of 8 A for the single group.
How much process data is used?
The sixteen output commands occupy two bytes of output process data.
Are the outputs internally short-circuit protected?
No. External fast fusing is required for each channel.
Which field terminals are needed?
DO562 uses one 9-pin and one 11-pin S500-eCo terminal block, ordered separately.
Is DO562 the same as DO561?
No. DO562 has sixteen outputs and two terminal blocks; DO561 has eight outputs and one 11-pin block.
Recommended Models
| XSP 534 | XTCEC012B10TD DILM12-10 | 3HE00029CAAA01 SP-GB-ZX-IDFC-AL |
| SSR-3F/BL | ir425/ir425-D4-2 | 3UL2304-1A |
| ABB TU844 3BSE021445R1 | SR3B261BD SR3XT141BD | RX7s-24 |
| GLB136-1E | 79CM30772 79CM307 | KV-700 |
| IG-3005-BPGK | 371-03694-000 | METSEPM5560 |
| ZG31/EX | 7PU4020-1AJ20 | 773100 |
| 6GK1905-6AA00 | RH 53A | M200E-SMB |
| 9002/13-280-110-00 | LBB4442 | SEM1700 |
| U539 | ESSER 804868 | SB-4Z-UN |
| 7101/IP1P E100 | 1492-FB1C30 | LQSE-4S1-D |