ABB TB5600-2ETH AC500 V3 Terminal Base
A compact terminal base for PM56xx-2ETH processors with controller power, local I/O expansion, two Ethernet ports, CAN and one serial interface.
Key Information
TB5600-2ETH is the most compact standard terminal base in the ABB AC500 V3 TB56xx range. It supports one processor module without adding a communication-module position, making it suitable where the processor interfaces cover the required network architecture.
The base concentrates controller power and field connections in a replaceable mounting assembly while the plug-in processor carries the automation program and processing resources.
Functions
- Provides the mechanical and electrical base for one compatible PM56xx-2ETH processor module.
- Presents ETH1 and ETH2 RJ45 ports for the processor network connections.
- Makes the processor CAN and COM1 interfaces available at the terminal base.
- Connects the processor to the local I/O bus for S500 expansion modules.
- Distributes the 24 V DC system supply through the removable five-pole spring terminal.
Specifications
| Manufacturer | ABB |
|---|---|
| Model | TB5600-2ETH |
| Order Code | 1SAP110300R0278 |
| Product Family | AC500 V3 |
| Processor Positions | 1 |
| Communication-Module Positions | 0 |
| Ethernet Interfaces | 2 x RJ45 |
| Additional Interfaces | 1 x CAN and 1 x COM1 serial |
| Supply | 24 V DC through removable 5-pole spring terminal |
| Maximum Current Consumption | 0.25 A including installed system components |
| Protection | IP20 |
| Mounting | 35 mm DIN rail or screw mounting; horizontal or vertical |
Installation
- Use only with a PM56xx-2ETH processor and verify the processor order code before assembly.
- Mount on a 35 mm DIN rail with 7.5 mm or 15 mm depth, or use 4 mm screws tightened to 1.2 N·m.
- Install and remove the processor or field wiring only under the safe isolation procedure defined for the control cabinet.
- Keep the RJ45, CAN, COM1, supply and I/O-bus connections accessible for commissioning and service.
- Select horizontal or vertical mounting while maintaining the clearances and environmental limits required for the complete AC500 station.
Lifecycle
- The standard TB5600-2ETH order code is listed by ABB in the Active lifecycle phase.
- TB5600-2ETH and the wide-temperature TB5600-2ETHC-XC are separate products; their order codes must not be interchanged.
- For service planning, retain the processor type, terminal-base order code, connection map and local I/O arrangement.
- A replacement terminal base should be checked against the installed PM56xx-2ETH processor and cabinet mounting footprint before changeover.