Home>TSI>Bently Nevada 3500/65 145988-02 16-Channel Temperature Monitor

Hot Categories

Bently Nevada 3500/65 145988-02 16-Channel Temperature Monitor

Bently Nevada 3500/65 145988-02 16-Channel Temperature Monitor

Item NO.: 3426613

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameBently Nevada 3500/65 145988-02 16-Channel Temperature Monitor
  • Item NO.3426613
  • Weight0.9100 kg = 2.0062 lb = 32.0993 oz
  • CategoryTSI
  • BrandBently Nevada
  • Creation Time2025-10-31
BENTLY NEVADA 3500/65 | 16 TEMPERATURE CHANNELS | PART 145988-02

Bently Nevada 3500/65 145988-02 16-Channel Temperature Monitor

The 145988-02 monitor spare for 16-channel RTD and isolated-tip thermocouple supervision in a 3500 rack.

BrandBently Nevada
Model3500/65 145988-02
Product Type3500/65 16-Channel Temperature Monitor
01

Key Information

3500/65 145988-02 is the monitor module spare for the Bently Nevada 3500/65 16-channel temperature monitor. It accepts RTD and isolated-tip thermocouple inputs and applies configured Alert and Danger supervision.

Channel configuration is set in 3500 software and may combine supported sensor types. The monitor, I/O module, channel map, firmware and rack software minimums must be reviewed as one replacement boundary.

02

Functions

  • Acquires as many as sixteen temperature channels.
  • Supports thermocouple types E, J, K and T.
  • Supports three-wire and four-wire RTD configurations.
  • Provides programmable under-temperature and over-temperature Alert and Danger setpoints.
  • Reports OK, transmit/receive and bypass status through front-panel indicators.
03

Specifications

Manufacturer Bently Nevada, a Baker Hughes business
Model 3500/65 145988-02
Part Number 145988-02
Product Family 3500 machinery protection system
Product Type 16-channel temperature monitor
Input Types Isolated-tip thermocouple or RTD
Thermocouple Types E, J, K and T
RTD Wiring 3-wire or 4-wire
Display Resolution 1 °C or 1 °F
Nominal Power Consumption 3 W
Input Impedance Greater than 1 MΩ per lead
Alert Delay 1 to 60 seconds in 1-second increments
Danger Delay 1 to 60 seconds in 0.5-second increments
Operating Temperature -30 to 65 °C
Storage Temperature -40 to 85 °C
Rack Position One full-height front slot with matching rear I/O slot
Internal-I/O Module 172103-01
External-I/O Module 172109-01; external terminal block 172115-01
04

Installation

  • Back up the 3500 rack configuration, channel sensor types, setpoints, delays and relay logic.
  • Record the 145988-02 label, monitor firmware, I/O-module part number, rack slot and every field channel.
  • Confirm the required 3500/22, configuration-software and display-firmware support before installation.
  • Do not pair an external termination block with an internal-I/O module arrangement.
  • Simulate every used RTD or thermocouple channel and prove indication, OK status, alarms, bypass and associated relay logic.
05

Lifecycle

  • Keep monitor and I/O revisions, firmware, rack configuration and calibration results together.
  • Review I/O-revision instructions before an upgrade; complete the prescribed firmware process with the I/O removed when required.
  • Inspect terminal blocks, sensor wiring and cold-junction or lead compensation behavior during outages.
  • Use event history to separate field-sensor faults from monitor or I/O faults.
07

FAQ

What must be supplied for an exact 3500/65 145988-02 quotation?

Provide both module labels, I/O part number, rack slot, firmware, 3500 software release, sensor list and channel configuration export.

Can 3500/65 145988-02 use internal and external terminations interchangeably?

No. Match the monitor to the correct I/O-module and termination architecture; an external terminal block is not used with the internal-I/O arrangement.

What compatibility checks precede a 3500/65 145988-02 firmware or I/O change?

Review the published minimum firmware and software levels, the installed 3500/22 and display firmware, and the I/O-revision procedure.

How should 3500/65 145988-02 be acceptance-tested?

Simulate each configured sensor type at several temperatures, then verify readings, OK state, Alert and Danger timing, bypass and relay action.

What information helps diagnose a 3500/65 145988-02 channel fault?

Include sensor type, wiring method, I/O revision, channel configuration, measured lead resistance, terminal photographs and event records.