Home>DCS>Emerson KJ3002X1-BG2 12P1731X082 Thermocouple / mV Input Card

Hot Categories

Emerson KJ3002X1-BG2 12P1731X082 Thermocouple / mV Input Card

Emerson KJ3002X1-BG2 12P1731X082 Thermocouple / mV Input Card

Item NO.: 3439726

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameEmerson KJ3002X1-BG2 12P1731X082 Thermocouple / mV Input Card
  • Item NO.3439726
  • Weight0.2000 kg = 0.4409 lb = 7.0548 oz
  • CategoryDCS
  • BrandEmerson
  • Creation Time2025-11-12
DeltaV S-series Traditional I/OCONTROLLED PRODUCT RECORD
THERMOCOUPLE / MV INPUT · LOCALBUS · EIGHT-CHANNEL FIELD INTERFACE

Emerson KJ3002X1-BG2 Thermocouple / mV Input Card

An Emerson DeltaV thermocouple and millivolt input card with eight field channels and LocalBus power.

LocalBus power12 VDC at 350 mA
Field channels8
Key positionB2
PRODUCT RECORD

Overview

Emerson KJ3002X1-BG2 is an eight-channel thermocouple and millivolt input card for a DeltaV S-series Traditional I/O subsystem.

The manufacturer sheet identifies 12 VDC at 350 mA LocalBus power and an isolated field circuit of 5.5 VDC at 0.6 mA per channel. The card uses key position B2.

Emerson states that the unit requires no calibration and contains no user-serviceable parts. Hazardous-area removal and insertion conditions remain part of the approved maintenance procedure.

PUBLISHED DATA

Specifications

Manufacturer
Emerson
Exact model
KJ3002X1-BG2
Input type
Thermocouple / millivolt
Field channels
8
LocalBus power
12 VDC at 350 mA
Field circuit
5.5 VDC at 0.6 mA per channel
Ambient temperature
0 to +60 °C
Shock
10 g half-sine, 11 ms
Vibration
1 mm peak-to-peak at 5–16 Hz; 0.5 g at 16–150 Hz
Humidity
5–95%, non-condensing
Enclosure rating
IP20
Airborne contaminants
ISA-S71.04 Class G3
Key position
B2
Calibration
Not required
ENGINEERING VIEW

Features

A

Eight-channel acquisition

Provides eight documented thermocouple or millivolt field-input channels.

B

Defined LocalBus load

The 12 VDC, 350 mA LocalBus requirement supports cabinet power review.

C

Keyed hardware fit

Key position B2 is part of the physical selection boundary.

D

Maintenance simplicity

The manufacturer specifies no calibration and no user-serviceable parts.

FIELD USE

Applications

APPLICATION

Temperature measurement

Acquiring compatible thermocouple signals in a DeltaV Traditional I/O installation.

APPLICATION

Low-level voltage input

Bringing documented millivolt signals into the assigned eight-channel card.

APPLICATION

Controlled card exchange

Replacing the exact card after channel types, cold-junction context and terminal identity are recorded.

SERVICE CONTROL

Lifecycle

CAPTURE

Capture

Record KJ3002X1-BG2, carrier position, keying, terminal block, channel types and configured ranges.

CONTROL

Protect

Follow the hazardous-area power and insertion conditions in the applicable Emerson procedure.

VERIFY

Validate

Verify each channel with an approved source and document polarity, range, alarms and cold-junction behavior.

IndustryParts industrial automation support team
INDUSTRIAL AUTOMATION SUPPLY SUPPORT

About IndustryParts

https://www.industryparts.com/

Documented handling for KJ3002X1-BG2

IndustryParts keeps the exact model, requested quantity, installed-system evidence and delivery record together so the proposed supply can be checked against the real application before dispatch.

Exact label retained
Application evidence reviewed
Packing record kept traceable
BUYER QUESTIONS

FAQ

Q01

How many field channels does KJ3002X1-BG2 provide?

The Emerson technical sheet identifies eight thermocouple or millivolt input channels.

Q02

What LocalBus load should be reserved for KJ3002X1-BG2?

Use the manufacturer value of 12 VDC at 350 mA in the carrier and power-budget review.

Q03

Does KJ3002X1-BG2 require periodic calibration?

No. Emerson states that the card does not require calibration and has no user-serviceable parts.

Q04

What evidence should accompany a KJ3002X1-BG2 enquiry?

Provide the full label, key position, carrier and terminal identities, channel sensor types, configured ranges and quantity.

Q05

What proves KJ3002X1-BG2 is ready after replacement?

Source-test every affected channel and confirm polarity, engineering range, cold-junction behavior, alarms and normal controller values.

You May Also Like