Home>PLC>Siemens 6ES7151-7FA21-0AB0 ET 200S IM151-7 F-CPU

Hot Categories

Siemens 6ES7151-7FA21-0AB0 ET 200S IM151-7 F-CPU

Siemens 6ES7151-7FA21-0AB0 ET 200S IM151-7 F-CPU

Item NO.: 3745928

Warranty: 1 year 


Condition : brand new in factory sealed box


Email: sales@mvme.cn


Chat online: +86 18030175807

Detail

  • Product NameSiemens 6ES7151-7FA21-0AB0 ET 200S IM151-7 F-CPU
  • Item NO.3745928
  • Weight0.2590 kg = 0.5710 lb = 9.1360 oz
  • CategoryPLC
  • BrandSiemens
  • Creation Time2026-08-24
  • SIMATIC DP ET 200S IM151-7 F-CPU
Siemens 6ES7151-7FA21-0AB0 ET 200S IM151-7 F-CPU

Siemens 6ES7151-7FA21-0AB0 ET 200S IM151-7 F-CPU

ManufacturerSiemensModel6ES7151-7FA21-0AB0Product TypeSIMATIC DP ET 200S IM151-7 F-CPU

01Technical Summary

Siemens 6ES7151-7FA21-0AB0 is an IM151-7 F-CPU for the ET 200S distributed I/O system. It combines local CPU processing with fail-safe automation capability and an integrated PROFIBUS DP interface that operates as a DP slave. The module provides 192 KB of work memory, uses a SIMATIC Micro Memory Card, and requires coordinated standard and safety engineering. Replacement therefore depends on the complete STEP 7 project, safety program, F-parameters, station layout, PROFIBUS configuration and acceptance documentation.

Configuration ControlVerify the full article number, installed hardware, electrical design, interfaces, wiring, software and lifecycle requirement before ordering.

02Specifications

Manufacturer Siemens
Article Number 6ES7151-7FA21-0AB0
Product Designation IM151-7 F-CPU
System SIMATIC DP ET 200S
Controller Type Fail-safe distributed CPU
Work Memory 192 KB
Memory Card SIMATIC Micro Memory Card required
Maximum Memory Card Capacity 8 MB
Integrated Interface PROFIBUS DP, 9-pin D-sub
PROFIBUS Role DP slave
Rated Supply 24 V DC
Permissible Supply 19.2-28.8 V DC
Power-Failure Bypass 5 ms
Typical Current Consumption 320 mA; 410 mA with DP master module
Typical Power Dissipation 4.2 W
Lifecycle Spare part / product cancellation

03Features

Key Functions

  • Executes standard and fail-safe program sections in a distributed ET 200S controller.
  • Provides 192 KB of work memory for the combined automation project.
  • Connects to PROFIBUS DP through the integrated 9-pin interface in DP-slave operation.
  • Uses a SIMATIC Micro Memory Card for program and configuration handling.
  • Supports deterministic local processing of the configured ET 200S station without a separate rack CPU for every task.
  • Includes controller diagnostics and status information required for commissioning and maintenance.

Identification

  • Manufacturer: Siemens
  • Model: 6ES7151-7FA21-0AB0
  • Product Type: SIMATIC DP ET 200S IM151-7 F-CPU
  • Status: Fail-safe legacy CPU

04Compatibility

  • Match the complete F-CPU article number, hardware release, firmware, STEP 7 version and safety-engineering package.
  • Preserve the SIMATIC Micro Memory Card, standard program, safety program, F-signature, F-parameters and passwords.
  • Verify the PROFIBUS address, DP-master project, telegram and any DP master module used with the F-CPU.
  • Check every ET 200S power, terminal, standard I/O and fail-safe I/O module against the saved station configuration.
  • Do not substitute a standard IM151-7 CPU for a fail-safe IM151-7 F-CPU.
  • Any hardware, firmware, wiring or safety-program change requires the applicable validation and acceptance process.

05Replacement

  • This exact F-CPU is a legacy spare-part and product-cancellation item; verify current Siemens service availability.
  • Create a complete project and memory-card backup before removal and document the F-signature and safety acceptance baseline.
  • Record the PROFIBUS topology, address, station layout, supply arrangement and all standard and fail-safe I/O assignments.
  • A migration to another controller family is an engineered safety project, not a part-number substitution.
  • After replacement, verify the F-signature, safety acceptance tests, PROFIBUS communication, all I/O, alarms, interlocks and machine sequence.

06FAQ

What is Siemens 6ES7151-7FA21-0AB0?

It is a fail-safe IM151-7 CPU for a SIMATIC ET 200S distributed I/O station.

How much work memory is integrated?

The official technical data specifies 192 KB of work memory.

Is a memory card required?

Yes. The module uses a SIMATIC Micro Memory Card, with capacities up to 8 MB documented for the CPU.

How does it connect to PROFIBUS?

It has an integrated 9-pin PROFIBUS DP interface and operates as a DP slave in the documented configuration.

Can a standard IM151-7 CPU replace it?

No. A standard CPU does not replace the fail-safe functions or safety validation of the IM151-7 F-CPU.

What must be validated after replacement?

Validate the F-signature, standard and safety programs, PROFIBUS, all standard and fail-safe I/O, diagnostics, alarms and safety functions.

You May Also Like