Yokogawa ADV551-P50 CENTUM VP 32-Channel Isolated Digital Output Module
A 32-channel isolated 24 V DC output module with the P-function execution and no status display.
Technical Summary
PRODUCT CONTEXTADV551-P50 is the Yokogawa ADV551 digital output module with thirty-two isolated 24 V DC channels. The P suffix adds pulse-width output and time-proportional output functions, while 50 identifies the no-display, non-explosion-protected basic execution.
The complete suffix must remain visible because adjacent ADV551 variants change status-display and environmental options. The field termination option is selected separately and must match the installed cable or terminal block.
Specifications
CONTROLLED DATA32, isolated
24 V DC
P: pulse-width and time-proportional output
Not included
No explosion protection
Basic type
ATD5A, ATD5S or ATD5D options as specified
107.5 × 32.8 × 130 mm
Features
FUNCTIONAL DISTINCTIONSThirty-two isolated outputs
Provides dense field switching in a single CENTUM VP FIO module.
Time-proportional control
The P execution supports pulse-width and time-proportional output functions.
Clear suffix boundary
P50 distinguishes the functional and front-display selection from nearby ADV551 variants.
Multiple termination routes
Dedicated cable and pressure-clamp terminal options support different cabinet architectures.
Compatibility
SELECTION BOUNDARIESOutput loads
Confirm voltage, steady and inrush current, switching rate and suppression for every field load.
Termination assembly
Match the installed ATD5A, ATD5S or ATD5D interface and any surge-absorber option.
Project configuration
Retain channel allocation and pulse-width or time-proportional settings from the FCS project.
Replacement
SERVICE WORKFLOWCapture
Save the project and record ADV551-P50, termination option, channel schedule and load details.
Transfer
Isolate field energy and move the exact cable or keyed terminal assembly under the approved procedure.
Prove
Test every used output, including timing behavior and safe-state response, before return to service.
FAQ
CUSTOMER DECISION SUPPORTWhat does the P suffix add to ADV551-P50?
It identifies the pulse-width output and time-proportional output function.
Does ADV551-P50 include a status display?
No. The 5 selection denotes the version without the front status display.
What should accompany a ADV551-P50 order?
Provide the complete P50 label, termination option, FCS slot, channel schedule and field-load record.
Can an ADV551 variant with a different final digit replace ADV551-P50?
Not automatically; the environmental option and other suffix-controlled features must be checked.
How should ADV551-P50 be commissioned?
Prove each active output, commanded timing, connected load response and controller diagnostics.